17
Figure 12: Wiring box connection options
(1)
(2)
(5)
(7)
(3)
(4)
(1) Fuse Holders
(2) RS485 Termination
(3) PV Positive Terminals
(4) PV Negative Terminals
(5) AC side Grounding Terminals
(6)
(6) AC side Neutral
(7) AC side L2
(8) AC side L1
(9) RS485 communication ports
Terminals in figure 12
Wire size permitted
Required torque
3-8 (see location and descripti-
on above)
14 - 6 AWG (2.5 - 16 mm2)
10.5 in-lbs (1.2 Nm)
Required torques for wiring box terminals
Table 1: Required torques for wiring box terminals
(9)
(8)