SOLE EUROSTAR ECO 125-1-S150 Installation & User Manual Download Page 16

15

5. Flat roof

Assembly instructions for systems with 1 collector:

Models: 125-1-S150, 125-1-S200, 150-1-S200, 150-1-S230, 200-1-S200, 200-1-S230, 200-1-S260

Assembly steps:

5.1.

Open  the  pack  of  the  support  system. Identify the  items  from  table  (page 5)  and  the  drawing  next
page.

5.2.

Assembly the parts between themselves using the set of bolts and nuts included in the pack. At this
stage do not fasten tight the bolts.

5.3.

Fix collector on support as shown on drawing using the M6X20mm bolts and washers (No. 22-23). Do
not fasten tight yet.

5.4.

Position the tank on supports. Two people are needed to handle it from each end. Fasten well with
the 2 bolts M10X30 the tank on the support system. (The 2 bolts are already mounted on the tank and
have to be temporarily removed before placing the tank on the support).

5.5.

Now, fasten  well the  collector  on  support  and then  fasten  well all  the  parts  of  the  support  system
among themselves.

5.6.

Drill the “floor” with 10mm drill at the 4 fixing points, insert the raw-plugs provided, and fasten well the
whole support system to the “floor”. Make sure that the material of “floor” is suitable (concrete) for this
kind of fixing, in order to withstand up to 97,2 Km/hr wind speed. If in doubt, consult your supplier, or
your engineer for possible alternative way of fixing.

5.7.

Connect the insulated copper (or plastic) pipe at closed loop system. The long pipe is for cold return
to bottom of collector. The short pipe is for hot supply from top of collector. Make sure that you fasten
well the “compression” fittings in order to tight the closed loop.

5.8.

Connect  the  non-return  pressure  safety  valve  on  the cold  water  inlet  of  tank,  making  sure  that  the
arrow is pointing towards the tank (upwards) and the escape outlet is facing sideways parallel to the
tank.

5.9.

Connect  cold  water  supply  using  always  a  shut-off water  valve. (Make  sure  the  pipes  are  well
insulated)

5.10.

Connect  hot  water  outlet  piping  to  consumption  points. It  is  strongly  recommended to  install  a
thermostatic  mixing  valve  set  at 55

o

C  on  the  hot  water  piping  anywhere  before  the  consumption

points. (Make sure the pipes are well insulated).

5.11.

Fill the tank with cold water. Leave open one “tap” of hot water, so that air will be flushed out and the
tank will be completely filled up.

5.12.

Fill up the closed loop system with thermo-convention liquid from the top pipe (point 15). Make sure
that no air-bubbles are coming out so filling is completed.

5.13.

Screw the  bronze  cap  with  the  copper  ring  on  the  filling point  to  seal  the  closed  loop  system.  The
closed loop is permanently sealed.

5.14.

Check for leakages on open or closed loop system.

5.15.

The (optional) electric heater should be connected by a fully licensed electrician following the national
standards for electric installations.

Connections points on thermostat:

No 1 : Line L (220 volt)
No 4 : Neutral N

On metal flange:

..

: Earth

Summary of Contents for EUROSTAR ECO 125-1-S150

Page 1: ...USERS MANUAL DOMESTIC SOLAR WATER HEATER THERMOSIPHON SYSTEM CLOSED CIRCUIT MODELS EUROSTAR ECO 125 1 S150 125 1 S200 150 1 S200 150 1 S230 150 2 S150 200 1 S200 200 1 S230 200 1 S260 200 2 S200 300 2...

Page 2: ...5 1 S150 125 1 S200 150 1 S200 150 1 S230 200 1 S200 200 1 S230 200 1 S260 15 Assembly instructions for systems with 2 collectors 17 Models 150 2 S150 200 2 S200 300 2 S200 300 2 S230 17 7 Inclined ro...

Page 3: ...012 A11 2014 IEC 60335 1 2010 Household and similar electrical appliances Safety Part 1 General requirement EN 60335 2 21 2003 A2 2008 IEC 60335 2 21 2002 A2 2008 Household and similar electrical appl...

Page 4: ...ng life Additionally it is protected against rusting with a large magnesium anode The ecologic polyurethane foam insulation guaranties minimum thermal loses even at very low ambient temperatures The e...

Page 5: ...nstalled at 3 different inclinations 20o 30o 40o so it can meet any roof slope The support system can withstand wind velocity up to 97 2 km hr and weight of snow up to 64cm height In order to assembly...

Page 6: ...ted long pipe 15mm for close loop cold water 1 56m 1 56m 2 07m 2 07m 1 85m 2 07m 2 07m 2 25m 2 25m 2 10m 2 22m 10 Insulated short pipe 15mm for close loop hot water 0 42m 0 42m 0 48m 0 38m 0 69m 0 50m...

Page 7: ...ould always be during transport and storage placed in horizontal position with the glass facing on top otherwise there is danger of water entering in the collectors from the ventilation holes at the b...

Page 8: ...ping outlets of the boiler so that it cannot slip 3 8 In cases where the solar system is large and the hot water consumption is low the hot water in the solar tank may reach temperatures up to 90o C I...

Page 9: ...pany to prevent from frost 4 4 On the hot water supply piping install a reliable thermostatic mixing valve set at 55o C to prevent higher temperature hot water to reach the consumption points 4 5 The...

Page 10: ...9 4 7 Thermal Performance of the System Model 125 1 S150 Model 125 1 S200...

Page 11: ...10 Model 150 1 S200 Model 150 1 S230...

Page 12: ...11 Model 150 2 S150 Model 200 1 S200...

Page 13: ...12 Model 200 1 S230 Model 200 1 S260...

Page 14: ...13 Model 200 2 S200 Model 300 2 S200...

Page 15: ...14 Model 300 2 S230...

Page 16: ...stic pipe at closed loop system The long pipe is for cold return to bottom of collector The short pipe is for hot supply from top of collector Make sure that you fasten well the compression fittings i...

Page 17: ...16...

Page 18: ...tom of collector The short pipe is for hot supply from top of collector Make sure that you fasten well the compression fittings in order to tight the closed loop Fix and fasten well the 2 compression...

Page 19: ...18...

Page 20: ...ated copper pipes at closed loop system The long pipe is for cold return to bottom of collector The short pipe is for hot supply from top of collector Make sure that you fasten well the compression fi...

Page 21: ...20...

Page 22: ...e long pipe is for cold return to bottom of collector The short pipe is for hot supply from top of collector Make sure that you fasten well the compression fittings in order to tight the closed loop F...

Page 23: ...22...

Page 24: ...ference which means that the natural recirculation is functioning 3 There is no leakage at the closed loop or open loop circuit 4 All bolts and nuts of the support system have been tightened very well...

Page 25: ...anode contact your installer Every 4 years check and paint if necessary with grey color primer the support frame At extremely cold winter nights below 0o C leave a hot water tap inside house slightly...

Page 26: ...NOTES...

Page 27: ...ed December 2015 version 5 SOLE S A SOLAR DOMESTIC APPLIANCES MANUFACTURER Lefktron Laikon Agonon 136 71 Acharnai Athens Greece Tel 30210 2389500 Fax 30210 2389502 Email export sole gr www eurostar so...

Reviews: