General. • 5 

2.4.3

 

By- Pass 

30A, 8310VA, 277VAC. (Maximum ratings) 
The SOLSTART-1P incorporates a change-over internal by-pass. While starting, the by-pass allows current flow 
through the thyristor.  At the end of the starting process the by-pass closes and carries the current to the Motor. 
The by-Pass is responsible for 2 functions at the end of acceleration: 

1.

 

The NO contact closes, shortens soft starter’s thyristor and bypasses it. 

2.

 

The NC contact opens and disconnecting the Starting booster (If exist – Consult factory for 
utilizing a starter booster) 

 

2.4.4

 

Starting Voltage adjustment 

The SOLSTART-1P incorporates a potentiometer (P15) allows the user to adjust the starting voltage of the motor thus 
controlling motor’s current and starting time.  
 
 

2.4.5

 

Additional current limiting 

In case of high starting current it is possible to add a starting buster to decrease the starting current. 
Consult factory for additional information. 
 
2.5

 

Signal reading with and without “SOLSTART-1P” 

 

________________________________________________________________________________________________________ 

 

DOL starting without soft-
starter and current limiter 

Soft-Starting with the 

“SOLSTART-

1P”

soft-starter and the current limiter 

Shown below are signal readings with and without the 

“SOLSTART-1P”

 

 
 

CAUTION! 

Power factor correction capacitors, if any, must not be installed on starter's Load side. 
When required, Install capacitors on the Line side. 

WARNING! 

When Mains voltage is connected to the starter, full voltage will appear on the starter’s 
load terminals. Therefore, for isolation purposes it is required to connect an isolating 
device (C/B, switch, etc) upstream to the SOLSTART-1P (on the Line Side). 

Summary of Contents for Solstart-1P

Page 1: ...t ta ar rt t 1 1P P M Mi in ni ia at tu ur re e S Si in ng gl le e P Ph ha as se e S So of ft t S St ta ar rt te er r 1 1 1 18 8A A 2 23 30 0V V I In ns st tr ru uc ct ti io on n M Ma an nu ua al l Ve...

Page 2: ...tarting Conditions 4 2 4 2 Mains Voltage line to line 4 2 4 3 By Pass 5 2 4 4 Starting Voltage adjustment 5 2 4 5 Additional current limiting 5 2 5 Signal reading with and without SOLSTART 1P 5 2 6 Wi...

Page 3: ...1 4 For further information see Technical Specification 1 3 Warnings 1 Internal components and P C Bs are at mains potential when the SOLSTART 1P is connected to mains This voltage is extremely dange...

Page 4: ...mm Weight Kg 18 Solstart 1P P1 130x50x40 0 2 2 4 Starter Selection The starter should be selected in accordance with the following criteria 2 4 1 Motor current Starting Conditions Select the starter a...

Page 5: ...time 2 4 5 Additional current limiting In case of high starting current it is possible to add a starting buster to decrease the starting current Consult factory for additional information 2 5 Signal r...

Page 6: ...pation Do not mount the starter near heat sources Protect the starter from dust and corrosive atmospheres Surrounding air temperature in the cabinet should not exceed 40 C 3 3 Temperature range heat d...

Page 7: ...not shown on this drawing 2 Contact factory for different kind of motor than shown on this drawing 4 2 Connection with Starting booster Note 1 Consult factory to utilize this application Solstart 1P B...

Page 8: ...n the PCB 4 Make sure motor is connected to neutral not via the SOLSTART 1P 5 Connect wire to the motor from point M indicated on the PCB 6 Leave wire B not connected and isolated Wire B is used for S...

Page 9: ...ter motor ends starting Yes Yes No No Rotate potentiometer P15 c c w by 20 Consult factory Startup procedure ends Rotate potentiometer P15 to its maximum c w Note By Pass should change its position ab...

Page 10: ...ent Supply voltage One phase line to line 220 240 Vac 10 15 Frequency 50 60 Hz Load Single Phase Two Wire Squirrel Cage Induction Motor Degree of protection IP 00 Altitude Up to 1000 m above sea level...

Reviews: