Table 8 1 Maintenance checklist and interval

.

8 Maintenance

Before maintaining and commissioning inverter and its peripheral

distribution unit switch off all the charged terminals of the inverter

,

and wait at least 10 minutes after the inverter is powered off

.

inverter output

status

Statistically maintain the status of

electrical yield and remotely monitor

,

its abnormal status

.

NA

Weekly

yearly

monthly

PV inverter

cleaning

Check periodically that the heat sink is

free from dust and blockage

.

Clean periodically

the heat sink

.

WARNING

8 1 Routine Maintenance

.

Check Item

Check Content

Maintenance

Interval

Maintain

content

PV inverter

running

status

Check that the inverter is not damaged

or deformed

.

Check for normal sound emitted during

inverter operation

.

Check and ensure that all inverter

communications is running well

.

If there is any

abnormal

phenomenon

,

replace the

relevant parts

.

Semiannually

PV inverter

Electrical

Connections

Check that AC DC and communications

,

,

cables are securely connected

;

Check that PGND cables are securely

connected

;

Check that cables are intact and there

are not wire aging

;

If there is any

abnormal

phenomenon

,

replace the cable

or re connect it

-

.

41

Summary of Contents for X3 Hybrid Series

Page 1: ...ion or individual should not plagiarize partially or fully copy incuding software ect and no reproduction or distribution of it in any form or by any means All rights reserved Solax Power Network Tech...

Page 2: ...k Application 2 3 Outline and Dimensions 2 4 Working Modes 2 1 1 Function 2 1 2 Model Description 2 3 1 Outline 2 3 2 Dimensions 2 2 1 Grid tied PV Power Systems 4 1 Checking the Outer Packing 4 2 Mov...

Page 3: ...of Connecting AC Cables 6 System Operation 6 1 R the Inverter un 6 2 Powering OFF the Inverter 7 User Interface 8 Maintenance 10 Disposal of the Inverter 11 Technical Specifications 8 1 Routine Maint...

Page 4: ...onnections operation commissioning maintenance and troubleshooting Please read through the manual carefully before installing and using the inverter and keep the manual well for future reference Grid...

Page 5: ...tuation which if not correctly followed could result in equipment failure to run or property damage Calls attention to important information best practices and tips supplement additional safety instru...

Page 6: ...ate on the inverter s enclosure because it contains important product information c Do not remove the anti dismantle label on the inverter s enclosure because it is the basis for product warranty 1 2...

Page 7: ...b Follow the procedures of commissioning described in the user manual when commissioning the PV inverter c Do not touch any other parts surface except the DC switch when the PV inverter is operating...

Page 8: ...nt safety and performance of the inverter rectify any faults that may compromise the inverter security performance before restarting the inverter 1 7 Additional Information To avoid any other unforese...

Page 9: ...V strings into AC power and feeds the power into power grid 2 1 2 Model Description Figure 2 1 shows a model number of the inverter using X3 50K TL as an example X3 50K TL Power class code Figure 2 1...

Page 10: ...C TN C S TT Inverter Inverter Inverter 2 2 1 Grid tied PV Power Systems This series applies to grid tied PV power systems for industrial commercial rooftops fishing farmers light complementary power...

Page 11: ...t of LED indicator area 1 PV Indicator 2 Grid Indicator 3 COM Indicator 4 Warning Indicator Figure 2 5 The rear view of this series inverter Figure 2 6 The bottom view of this series inverter Reserved...

Page 12: ...Figures 2 7 The dimensions of this series unit mm 2 3 2 Dimensions Figures 2 7 shows the dimensions of these series inverters as follows 855 500 275 9...

Page 13: ...requirements but cannot meet its minimum power requirements When the PV inverter is grid tied and generates electricity it tracks the maximum power point to maximize the PV String output converts DC p...

Page 14: ...relative humidity of 0 to 100 no condensing The PV inverter should be stored in a clean and dry place and be protected from dust and water vapor corrosion A maximum of layers of inverters can be stack...

Page 15: ...osive materials Do not install the inverter in a place where personnel are likely to come into contact with its enclosure and heat sinks to avoid electrical shock burn Figures 4 1 The deliverables The...

Page 16: ...th care Do not place the PV inverter with its wiring terminals contacting the floor because the power ports and signal ports at the bottom of the device are not designed to support the weight of the i...

Page 17: ...eds 10 minutes to finish discharge The PV inverter must not be touched when in operation Its enclosure and heat sinks are extremely hot Electrical shock This part is charged Only qualified and or trai...

Page 18: ...tail Support mounting wall mounting Basic Requirements a The inverter is protected to IP65 and can be installed indoors or outdoors b The installation method and position must be appropriate for the w...

Page 19: ...und the inverter to ensure sufficient space for installation and heat dissipation as shown in Figure 4 4 a The carrier where the inverter is installed must be fire proof Do not install the inverter on...

Page 20: ...elow are some correct wrong installation modes as shown in Figures 4 7 4 8 Figures 4 7 The correct installation mode The correct installation mode upright back tilt Figure 4 8 The wrong installation m...

Page 21: ...n the support and tighten the inverter with rear panel using screws as shown in Figure 4 11 Figure 4 11 Tightening the inverter Anti theft lock is recommended to be installed here Figure 4 9 The rear...

Page 22: ...ints on the rear side of the inverter align with the three holes of the support Ensure that the inverter is well fixed Ensure that the inverter in locked on the support and an antitheft lock is instal...

Page 23: ...ites An isolation transformer must be installed on the AC side of each inverter Ensure that the neutral wire of the isolation transformer must be disconnected from the PGND cable One isolation transfo...

Page 24: ...end by 2mm 3mm as shown in Figure 5 1 5 1 2 Wiring Procedures Figure 5 1 Stripped length unit mm The ground cable and OT terminals have been prepared with below requirements a Ground cable Outdoor mu...

Page 25: ...the crimping areas of the OT terminal and crimp them using hydraulic pliers as shown in Figure 5 2 Figure 5 2 Crimping a cable unit mm Step 3 Remove the ground screws from the ground points secure the...

Page 26: ...tection switch is stalled or else a power grid trip may occur 5 2 1 Preparation The AC power cable and AC terminals have been prepared with below requirements AC terminal 5 core outdoor special cable...

Page 27: ...nto the locking cap and the AC OUTPUT connector at the inverter bottom and connect the AC cable to L1 L2 L3 N and PE tighten them using screw driver and the required torque is 12 N m Step 2 Loosen the...

Page 28: ...the inverter is grid tied it is not allowed to maintain DC input power cables such as connect or disconnect a string or a module in a string Only after the inverter enters in shutdown mode it is allo...

Page 29: ...nverter model Connected to any route 30K 36K 50K 60K 36K 60K Connected to routes 2 6 Connected to routes 2 6 10 Connected to routes 2 6 10 13 Connected to routes 2 3 6 10 13 Connected to routes 2 3 6...

Page 30: ...and negative metal connectors are packed with positive and negative connectors respectively when shipped out After unpacking keep the positive and negative ones separate to avoid confusion Procedures...

Page 31: ...ve power cables into the corresponding positive and negative connectors until a click sound is heard as shown in Figure 5 10 Figure 5 10 Connecting positive and negative connectors Step 4 Tighten the...

Page 32: ...g terminals of the inverter until a click sound is heard as shown in Figure 5 13 Step 7 After connecting the PV strings ensure that all connectors are in position by checking for resistance when a sli...

Page 33: ...S refer user manual of accessory for connecting method and its setting Table 5 3 WIFI GPRS Modules Description RS485 GPRS module implements communication with Cloud server through cellular to monitor...

Page 34: ...ted note the following 1 No need for re setting Modbus address and the address can be allocated automatically if V1000 data logger is used Otherwise you need to re set Modbus address manually through...

Page 35: ...Connect RS485 differential positive and negative signal of data logger to terminal 1A and 1B of inverter and connect terminal 2A and 2B of the inverter to terminal 1A and 1B of another inverter To pre...

Page 36: ...ompt manual as shown in Figure 5 17 Figure 5 17 APP homepage setting SEBLE SE History Generating capacity Maintenance Setting Standby Mode Step 3 Check the Modbus address in Figure 5 18 the default ad...

Page 37: ...T DTSU666 5 5 2 Settings via APP Power Limit Power limit function Disable Power limit mode Power limit CT ratio 1000 1 Maximum feed in grid power W 0 Digital Power Meter Type Unknown Meter on Grid Pow...

Page 38: ...with 9600 BPS 8 data bit 1 stop bit no parity data format with communication address 1 Please make sure that the meter is set to Modbus RTU 9600 8 N 1 with address 1 About digital meter setting opera...

Page 39: ...minals using multimeter 6 Waterproof connectors at AC terminals and RS485 ports are plugged with waterproof plugs tightly 7 Covers at AC terminals are tightened 8 Idle terminals are sealed 9 All safet...

Page 40: ...enough energy 2 Observe statuses of LED indicator lights on the inverter according to Table 7 2 Please set the inverter if it is the first time to start up Above steps are for the regular start of th...

Page 41: ...on blink Grid Indicator on blink Status Power grid abnormal The conditions for feed in operation are not yet met Feed in operation The blink every cycle lasts 30s of the times grid indicator present p...

Page 42: ...response modes please refer to APP User Manual Figure 7 1 Setting power quality response modes Warning code PV indicator Grid indicator COM indicator Warning indicator Normal status Starting up WLAN W...

Page 43: ...age Internal Communications Fault Software version incompatibility C7 C9 CA CB CC Remote off CN Note light on light off light blink keep original status 40 Control power abnormal DC bias current abnor...

Page 44: ...age Clean periodically the heat sink WARNING 8 1 Routine Maintenance Check Item Check Content Maintenance Interval Maintain content PV inverter running status Check that the inverter is not damaged or...

Page 45: ...PP 3 If the alarm persists for a long time check whether the AC circuit breaker AC terminals is disconnected or not or if the grid has a power outage Check the number of PV modules and adjust it if ne...

Page 46: ...g or deteriorated PV Strings Reverse The cables of PV strings are connected reversely during the inverter installation Check whether the cables of PV strings are correctly connected If they are connec...

Page 47: ...monitor displays no output voltage Output switch tripping Check if DC switch is damaged and if not switch it to ON If it still doesn t work contact your dealer Inverter off grid 1 Power grid fault 2...

Page 48: ...les as shown in Figure 8 1 Figure 8 1 Removing DC input connector When removing DC input connector insert the removal wrench to the bayonet press the wrench down and take out the connector carefully N...

Page 49: ...ny abnormal noise emitted from the fan replace the relevant parts timely In built PV FUSE are equipped in the inverter if any warning display that the FUSE is melt disconnect AC breaker and switch the...

Page 50: ...scretions provide paid service 1 The warranty period expired 2 The damage caused during transit 3 The damage caused by man 4 The damage caused by force majeure including but not restricted to the foll...

Page 51: ...erter and its packing case are made from environment friendly materials If the inverter service life has expired do NOT discard it with household garbage dispose the inverter in accordance with local...

Page 52: ...ut Grid Rated AC Active Power 29 000W 34 500W Max AC Apparent Power 33 000VA 40 000VA Max AC Active Power PF 1 33 000W 40 000W Max AC Output Current 3 83A 3 92A Rated AC Voltage 220V 3W N PE AC Voltag...

Page 53: ...ral Topology Transformerless IP Rating IP65 Night Self Consumption 1W Cooling Fan cooling Operating Temperature Range 25 60 Relative Humidity Range 0 100 Max Operating Altitude 4000m Noise 62dB Dimens...

Page 54: ...ower 50 000W 60 000W Max AC Apparent Power 50 000VA 60 000VA Max AC Active Power PF 1 55 000W 60 000W Max AC Output Current 3 76A 3 92A Rated AC Voltage 380V 400V 3W N PE AC Voltage Range 277V 520V Ad...

Page 55: ...275mm Weight 73Kg 74Kg HMI COM Display Wireless APP LED Communication RS485 WiFi GPRS 4G LAN Optional Certification Safety IEC62109 1 IEC62109 2 EMC EN 61000 6 2 4 Grid Code VDE AR N 4105 4110 EN 505...

Page 56: ...Shizhu Road Tonglu Economic Development Zone Dongxing District Tonglu City Zhejiang Province China 86 571 5626 0011 Tel info solaxpower com E mail 614 30166 03 Solax Power Network Technology Zhe jiang...

Reviews: