22/29
INSTRUCTIONS— GAS AIR HEATER -
MINIGAZ Eco
MH Eco, MC Eco, MV Eco– NT09004I-GB – 29/11/2017
C32 - for MV Eco 35
Combustion air is taken outside and by-products are released
outside. The connection is done vertically.
The KC32-80125V (ø 80/125)
is made of a vertical coaxial terminal
(1).
Roof water tightness will be made with a standard roof seal (5) or
hand made up according the kind of roof.
It is possible to shorten, lengthen or lead astray the flue
thanks to a wide range of flue accessories (pipes, elbows,…).
C32 - for MV Eco 50/60/80 type
Combustion air is taken outside and by-products are released
outside. The connection is done vertically.
The KC32-130200V
(ø 130/200) kit
is made of a vertical coaxial
terminal (1), an adaptive piece and of two pipes of 250 mm (2).
Roof watertight will be made with a standard roof seal or hand
made up according the kind of roof.
It is possible to shorten, lengthen or lead astray the flue
thanks to a wide range of flue accessories (pipes, elbows,
…).
5-5 Connection of vertical coaxial flue pipe - C32 - for MV Eco type
Junction shall be airtighted and rigid.
Flue pipes sections shall at less be equal to the starting section. Flue pipes shall be vertical or at the maximum with a
45 °angle.
Total length of flue shall not exceed 8 m ( taking into account than pressure drops in a 45° or 90° elbow are
similar to losses in a 1 m pipe).
If the length of the outside flue is more than 2 meters an insulation shall be installed
CAUTION
The use of airtight pipes implies a perfect air tightness of the junctions. Thus in order to make the assembly easy it is
necessary to use a non corrosive lubricant (for example: soap water).
Length of coaxial flue
1850 mm
Maximum length (coaxial flue + extension)
6 m
Outside diameter
200 mm
Diameter of pipe (fumes)
130 mm
Diameter of pipe (air)
130 mm
Length of coaxial flue
1155 mm
Maximum length (coaxial flue + extension)
6 m
Outside diameter
125 mm
Diameter of coaxial extension
125 mm
1
1
2