10/29
INSTRUCTIONS— GAS AIR HEATER -
MINIGAZ Eco
MH Eco, MC Eco, MV Eco– NT09004I-GB – 29/11/2017
C
3– GAS AIR HEATERS INSTALLATION
(see instructions provided with the brackets)
3-1 Advice for installation
In order to secure the operation of the appliance, please respect the hereafter indications:
-
A minimum distance of 430 mm between the wall and the back of the appliance shall be res-
pected.
-
Check that there is enough space for the door opening.
-
The appliance shall be installed at a minimum distance of 200 mm from the roof and 2000 mm
from the floor.
700 mini
200
m
ini
(*
)
200
mini
2000
m
ini
200
m
ini
2000
m
ini
200
m
ini
200
m
ini
(*
)
430
mini
3-2 List of standard supports
Reference codes:
Axial gas air heater
MH Eco 16 Eco 21 Eco 28 Eco 35 Eco 50 Eco 60 Eco 80 Eco
Rotating wall bracket
SMR
3500070
3500048
IPN fastening kit for SMR
KIPN
3500047
Fixed wall bracket
SMF
3500071
3500049
IPN fastening kit for SMF
KIPN1
3500074
Centrifugal gas air heater
(without dampers & filters)
MC Eco
21 Eco 28 Eco 35 Eco 50 Eco 60 Eco 80 Eco
Fixed wall bracket
SMF
3500049
Vertical gas air heater
MV Eco
35 Eco 50 Eco 60 Eco 80 Eco
Suspension bracket
SDS
3500050
3500067
(*) : See page 7 for MV Eco models