INSTRUCTIONS— GAS AIR HEATER -
MINIGAZ Eco
MH Eco, MC Eco, MV Eco– NT09004I-GB – 29/11/2017
5-4 Connection of vertical coaxial flue pipe - C32 - for MH and MC Eco ty
Junctions shall be airtight and rigid
Flue pipes sections shall at less be equal to the starting section. Flue pipes shall be vertical or at the maximum with a
45 °angle.
Total length of flue shall not exceed 6 m ( taking into account than pressure drops in a 45° or 90° elbow are
similar to losses in a 1 m pipe).
If the length of the outside flue is more than 2 meters an insulation shall be installed.
CAUTION
The use of airtight pipes implies a perfect air tightness of the junctions. Thus in order to make the assembly easy it is
necessary to use a non corrosive lubricant (for example: soap water).
C32 - for MH Eco 16/21/28/35 and MC Eco 21/28/35 type
Combustion air is taken outside and by-products are released outside. The connection
is done vertically.
The KC32-80125 (ø 80/125)
is made of a vertical coaxial flue (1) and of a 90° coaxial
elbow (2).
Roof water tightness will be made with a standard roof seal or hand made up
according the kind of roof.
It is possible to shorten, lengthen or lead astray the flue thanks to a wide range
of flue accessories (pipes, elbows,…).
The maximum length of the coaxial flue + its extension shall not exceed 6 m.
C32 - for MH Eco 50/60/80 and MC Eco 50/60/80 type
Combustion air is taken outside and by-products are released outside. The connection
is done vertically.
The
KC32-130200 (Ø130/200) kit
for MH/C Eco 50/60/80:
-1 vertical coaxial flue (1)
-
2 90° elbows – diam. 130 mm (2)
-
1 pipe - length 500 mm – diam. 130 mm
-
1 pipe –length 250 mm - diam. 130 mm
-
1 adaptive piece
Roof watertight will be made with a standard roof seal (5) or hand made up according
the kind of roof
It is possible to shorten, lengthen or lead astray the flue thanks to a wide range
of flue accessories (pipes, elbows,…).
The maximum length of the coaxial flue + its extension shall not exceed 6 m.
1
2
1
2
Length of coaxial flue
1155 mm
Maximum length (coaxial flue + extension)
6 m
Outside diameter of coaxial flue
125 mm
Diameter of coaxial extension
125 mm
KC32-130200
Length of coaxial flue
1850 mm
Maximum length (coaxial flue + exten-
sion)
6 m
Outside diameter
200 mm
Diameter of pipe (fumes)
130 mm
Diameter of pipes (air)
130 mm