28
Connection conditions for the single MPPT operating mode
■
■
Minimum conductor cross section: 95 mm
2
■
■
All the DC inputs of the inverters in use must be connected in parallel.
■
■
The DC bus bars for connecting the inverters in parallel must be dimensioned for the
maximum current:
Number of inverters
Maximum current in the DC bus bars [A]
2
720
3
960
4
1 440
■
■
All DC feed lines must be individually fitted with fuses, both at the plus as well as the
minus pole. Use 160 A NH fuses which have been certified for at least 1 000 VDC (the
160 A correspond to the max. DC total current of a MaxConnect combiner box).
■
■
Installation of a ground connection to one pole of the PV generator is permissible (plus
or minus pole).
DANGER
Fatal electric shock hazard! – When a pole of the PV generator is grounded (or func-
tionally grounded), that pole must be considered as live and must be insulated.