6 Heating circuit
6 Heating circuit
Abb. 2-26
1 Outside temperature
2 Average outside temperature
3 Room temperature
(optional)
4 Temperature of the energy source,
(e.g.boiler,
buffer tank)
5 Flow temperature of the heating circuit
6 Position of the heating circuit mixing valve
0% - the mixer is closed, the heating circuit is supplied
from the heating circuit return. 100% - the mixer is open,
the heating circuit is supplied from the heating boiler flow.
7 Info line: Heating request (Yes/No) to the
energy source
8 Status line of the heating circuit
9 Heating circuit settings
10 Display of the heating circuit operating mode
set on the optional room temperature con-
troller (Art. no. 6160)
6.1 Heating circuit settings
Abb. 2-27
1 Heating circuit operating mode
2 Room settings
(Button is only visible when the
Room influence
parameter
is set to
On
or
Sliding
; this can be found in the
Qualified
personnel system parameters)
3 General settings
4 Heating curve
6.1.1 Heating circuit operating mode
Heating mode
The heating circuit pump is activated. A shutdown
occurs whenever
–
the
cutoff temperature for heating mode
is rea-
ched.
–
a room temperature sensor is used and where
inside setpoint temperature for heating mode
has
been reached.
The heating circuit is supplied with the
calculated
required flow temperature
Reduced mode
Heating circuit pump is activated. A shutdown occurs
whenever
–
the
cutoff temperature for reduced mode
is rea-
ched.
–
a room temperature sensor is used and where
inside setpoint temperature for reduced mode
has
been reached.
The heating circuit is supplied with the reduced tem-
perature, i.e.
calculated required flow temperature
minus
reduction
20
Operation manual
pelletelegance