Communications
33
11.4
Remote Emergency Power Off
The UPS is equipped with a Remote Emergency Power Off (REPO) connector.
The user must supply a means of interfacing with the REPO circuit to allow disconnecting the UPS
input feeder breaker to remove all sources of power to the UPS and connected equipment to comply
with national and local wiring codes and regulations.
Figure 5
REPO switch connections
!
CAUTION
To maintain safety (SELV) barriers and electromagnetic compatibility, signal cables should
be segregated and run separately from power cables.
REPO connections
for normally open
switch system
REPO
as shipped
REPO connections
for normally closed
switch system (fail-safe)
1
2
3
4
Key to REPO switch connections
1.
24 VDC
2.
Sense
3.
Sense
4.
Ground
REPO Connection
1
2
3
4
1
2
3
4
Summary of Contents for S4K4U6000
Page 1: ...POWER AVAILABILITY S4K4U6000 USER MANUAL 120 208V On Line UPS 120 208V 120 240V...
Page 2: ......
Page 50: ...Specifications 44...
Page 51: ......