System Description
6
3.5
DC to DC Converter
The DC to DC converter utilizes energy from the battery system and raises the DC voltage to the opti-
mum operating voltage for the inverter. This allows the inverter to operate continuously at its opti-
mum efficiency and voltage, thus increasing reliability.
3.6
Battery
The S4K4U6000 utilizes valve-regulated, nonspillable, flame retardant, lead acid batteries. To main-
tain battery design life, operate the UPS in an ambient temperature of 68°F to 77°F (20°C to 25°C).
Optional external battery cabinets are available to extend battery run times.
3.7
Dynamic Bypass
The S4K4U6000 provides an alternate path for utility power to the connected load in the unlikely
event of a UPS malfunction. Should the UPS have an overload, overtemperature or UPS failure condi-
tion, the UPS automatically transfers the connected load to bypass. Bypass operation is indicated by
an audible alarm and illuminated amber Bypass indicator (other indicators may be illuminated to
indicate the diagnosed problem).
The user may manually transfer the connected load from the inverter to bypass by pressing the
Standby button once.
NOTE
The bypass power path does NOT protect the connected equipment from disturbances
on the utility supply.