Installation and Configuration
10
6.0
I
NSTALLATION
AND
C
ONFIGURATION
This section includes instructions on how to install, configure and perform initial electrical checks of
your UPS installation.
DO NOT attempt to start the UPS, turn on any circuit breaker or energize the input power until
instructed to do so in
7.0 - Initial Startup and Electrical Checks
.
Visually inspect the UPS for freight damage. Report damage to the carrier and your local dealer or
Sola/Hevi-Duty representative.
Install the UPS indoors in a controlled environment, where it cannot be accidentally turned off. Place
it in an area of unrestricted airflow around the unit, away from water, flammable liquids, gases, cor-
rosives and other conductive contaminants. Maintain a minimum clearance of 4" (100mm) in the front
and rear of the UPS. Maintain an ambient temperature range of 32°F to 104°F (0°C to 40°C).
6.1
Install the Main Cabinet
The S4K4U6000 may be installed either as a tower unit or in a rack, depending on available space
and use considerations. Determine the type of installation and follow the appropriate instructions in
either
6.1.1 - Tower UPS Installation
or
6.1.2 - Installing the Adjustable Rack-Mount Kit—
Sold Separately
.
6.1.1
Tower UPS Installation
When using the S4K4U6000 in a tower configuration, use the included support base (shown below,
left) to stabilize the UPS.
If any external battery cabinets are added, they will include spacers to accommodate the additional
cabinets (shown below, right).
Figure 2
Support base and spacers
!
CAUTION
The UPS is heavy (see
14.0 - Specifications
). Take proper precautions when lifting or
moving it.
NOTE
UPS operation in sustained temperatures above 77°F (25°C) reduces battery life.
4U Support Base
Spacers added to support
base to accommodate
additional battery cabinets
End Bases
2U Spacer