6
| important Safety Precautions
imPOrTAnT SAFETy PrECAUTiOnS
SAVE THESE INSTRUCTIONS
This manual contains important safety instructions. read all safety and operating instructions before operating the
Uninterruptible Power System (UPS). Adhere to all warnings on the unit and in this manual. Follow all operating and user
instructions. This equipment can be operated by individuals without previous training.
This product is designed for commercial/industrial use only. it is not intended for use with life support or other designated
“critical” devices. maximum load must not exceed that shown on the UPS rating label. The UPS is designed for data
processing equipment. if uncertain, consult your dealer or local SolaHD representative.
This UPS is designed for use on a properly grounded (earthed) 50 or 60 Hz supply. The factory default setting is 120/208 V ac,
60 Hz. installation instructions and warning notices are in this manual.
The S4KC is designed for use with a four-wire input (L1, L2, n, G).
!
wARNINg
Although the S4KC has been designed and manufactured to ensure personal safety, improper use can result in electrical
shock or fire. To ensure safety, observe the following precautions:
•
Turn off the UPS and disconnect it from the power source before cleaning.
•
Clean the UPS with a soft, dry cloth. Do not use liquid or aerosol cleaners.
•
Never block or insert any objects into the ventilation holes or other openings of the UPS.
•
If using the UPS power cord, place it in a location where it will not be damaged.
Operate the UPS in an indoor environment only, in an ambient temperature range of 0°C to +40°C (+32°F to +104°F).
Temperature Rating (all models):
Units are considered acceptable for use in a maximum ambient of +30°C for ambient
operation without derating. in addition, output derating (90%) may be applied for use in a maximum ambient between
+30°C and +40°C. Please see Table 8 for details of the derating declaration.
install the UPS in a clean environment, free from moisture, flammable liquids, gases, and corrosive substances.
The S4K4U6000C contains no user-serviceable parts. The S4K6U10KC contains no user-serviceable parts, except for the
power module. The UPS On/Off buttons do not electrically isolate internal parts. Under no circumstances should you
attempt to gain access internally due to the risk of electric shock or burn. The internal battery pack may be replaced by
qualified service personnel only.
Do not continue to use the UPS if the front panel indications are not in accordance with these operating instructions or
the UPS performance alters in use. refer all faults to your SolaHD representative.
DO nOT COnnECT equipment that could overload the UPS or demand dc current from the UPS, such as: electric drills,
vacuum cleaners, laser printers, hair dryers, or any appliance using half-wave rectification.
Storing magnetic media on top of the UPS may result in data loss or corruption.
The UPS handle is not for transit.