S4KC SEriES USEr mAnUAL |
51
Table 10: External Battery Cabinet Specifications
Parameters
Model Number
S4K144BATC
S4K288BATC
Used with
6000 VA models
10000 VA models
DIMENSIONS, w x D x H, in. [mm]
Unit (with bezel)
3.3 x 26.1 x 16.9 [85 x 662 x 430]
6.8 x 26.5 x 16.9 [173 x 672 x 430]
Shipping
25.8 x 34.3 x 12.3 [655 x 872 x 312]
13.2 x 33.1 x 24.5 [336 x 842 x 622]
wEIgHT, lb. [kg]
Unit (including internal batteries)
99.9 [45.3]
172.0 [78.1]
Shipping
110.2 [50.0] with internal batteries
44.1 [20.0] without internal batteries
BATTERy PARAMETERS
Type
Valve-regulated, non-spillable, flame retardant, lead acid
Qty x V x Rating
2 x 6 x 12 V x 8.5 Ah
2 x 12 x 12 V x 8.5 Ah
Battery Mfr./Part Number
Panasonic/UP- rW1245; CSB/Hr 1234W F2
Backup Time
See Table 13
ENVIRONMENTAL REqUIREMENTS
Operating Temperature
0°C to +40°C [+32°F to +104°F]; See Table 8 for operating temperature parameters
Storage Temperature
-15°C to +50°C [+5°F to +122°F]
Relative Humidity
0% to 95%, non-condensing
Operating Elevation
Up to 10,000 ft. [3,000 m]
AgENCy
Safety
UL1778, cUL Listed, not for use in a computer room as defined in the standard
for the protect of Electronic Computer/Data Processing Equipment AnSi/nFPA 75
RFI/EMI
FCC Part 15, Subpart B, Class A
Transportation
iSTA Procedure 1A