5.1.4

Data bus failures

Functioning of data bus is signalled by flashing of pair of yellow ”TXR” and ”RXR” LEDs, that signal transmitting
of a message into the bus (flashing of ”TXR” LED) and receiving of a message from the bus (flashing of ”RXR”
LED).

Data bus failures manifest themselves by full or partial malfunctioning of the bus communication. Module with
inoperative data bus communicates through its configuration port, responds to configuration commands, but the
messages from some of the connected meters (or from all of them) do not come to the radio network (or vice versa
- messages from the radio network don’t come to the devices on the bus.). In some cases the malfunction of the bus
is partial - interruptions are either random in time or their affect is limited to only some of the connected devices
(meters, sensors).

Data bus failures and breakdowns can be caused by following reasons:

incorrect setting of data bus parameters as decribed inparagraph

3.5.5

or discrepancy between bus parameters

of the module and connected device;

mechanical damage of the bus cable;

fault of module’s link amplifier;

worsening of the bus transmission capacity as a result of some changes or modifications of the bus (...a new
device connected to bus, order alteration, wiring replacement, terminator connection/disconnection...);

disturbance of the electrical signal within the bus by induction of the interfering signal into the bus, or troubles
caused by differences of electrical potential among devices connected to the bus.

Recommendation:

Troubles with bus transmission capacity as described in the last two items generally occur

especially if there is a bus with lengthy wiring and with high number of connected devices. Troubleshooting of the
bus failures can be quite complicated and requires a specific knowledge and experiences. It is recommended to entrust
the task to the specialist with experiences with given type of bus.

If there is a suspicion that the operational troubles with data collection from the remote bus could be caused by fail-
ure of data bus itself, first of all check correctness of data collection system settings, especially correct identification
(addressing) of individual devices within central system (master) database. If the correctness of the identification
is positively checked, proceed with troubleshooting of the data bus communication malfunctioning in following steps:

visually check whether the bus cable from the given meter/sensor is attached correctly to the module and test
its functionality by ohmmeter. If the inspection of the cable shows any signs of its damage (or it is evidently
inoperative), repair or replace the cable immediately;

if the bus wiring is undamaged and messages from other devices on the same bus came to the central system
correctly, check consistency of setting of bus parametres within the module configuration and within the
connected meter/sensor as described in the paragraph

3.5.5

Setting of parameters of the M-Bus bus”

if the bus is physically functional and its configuration is correct and consistent with setting of connected
devices, but the communication through the bus is still non-functional, the WM868-MS-LP-H module is
probably defective and it is necessary to make its replacement as described in the paragraph

4.7

;

if the bus communication will not work properly even after replacement of the module, the bus is physically
apparently functional, configuration of the module is correct, addressing is in harmony with setting of bus

Master”, but the messages still dont pass through the bus, the bus is probably not working correctly on

the data level. In this case try to make some changes in the bus setting on the

Master” side (different

speed, different Inter-Byte timeout...) that is possible to make and could have some influence on the bus
communication. In this case it is recommended to ask for advice/support some person with broad experiences
in bus communication or module producer.

5.2

Troubleshooting procedure

To identify a reason of device failure or any anomaly in its operation follow this procedure:

1. No data are available from any remote segment of WACO virtual bus. In this case it is recommended to check

functionality of the module subsystems in following order:

check functionality of power supplying as described in the paragraph

5.1.1

Power supplying failures”

check functionality of the system as described in the paragraph

5.1.2

System failures”

check bus functionality as described in the paragraph

5.1.4

Data bus failures”

check transmitting and receiving functionalities as described in the paragraph

5.1.3

Transmitter and

receiver failures”

WM868-MS-LP-H

28

Summary of Contents for WACO WM868

Page 1: ...WIRELESS COMMUNICATION SYSTEM WACO WM868 WM868 MS LP H Revision 3 0 SOFTLINK s r o Tomkova 409 278 01 Kralupy nad Vltavou Czech Republic Phone 420 315707111 e mail sales softlink cz www softlink cz...

Page 2: ...List of WM868 MS LP H module configuration parameters and commands 13 3 5 2 Configuration group of commands for writing of configuration and reset 14 3 5 3 Commands for settings of radio frequency su...

Page 3: ...O USB GateWay in the MS Windows Device Manager 7 10 Entering of devices and variables into the remote configuration window 8 11 Progress of getting values of preselected variables of the module by usi...

Page 4: ...ctionality description below the WM868 MS LP H module can be used in applications of M Bus RS 485 data bus systems that are commonly deployed in industrial automation as well as in the area of remote...

Page 5: ...ower supply 24V DC For connecting of the power supply there is a screw on terminal with marked voltage polarity Power supplying must follow all the safety requirements according to the appropriate sta...

Page 6: ...ssion speed 300 9600 Baud Operation mode asynchronous Transmission parameters default 8 data bits 1 stop bit none parity Signal level by EN1434 3 EN60870 Nominal current consumption 1 5 mA Power suppl...

Page 7: ...nel 3 1 1 Connecting of module to computer Configuration can be performed by using of common USB port of the computer For the interconnection with a USB port of computer it is necessary to use an manu...

Page 8: ...unication choose Serial option of the connection type in the Session tab Check or set up the communication speed Speed to 19200 bits s and then enter into the Serial line tab the number of the serial...

Page 9: ...entation otherwise you would be risking the unwanted command enter that might be the same as the ones used for manufacturer settings diagnostics or service and repair 3 2 Configuration of the module v...

Page 10: ...th analyzer but it is connected to the remote Ethernet IP port of the IP network Internet anywhere over the world provided that there is an IP connection between the computer and the GateWay see figur...

Page 11: ...then the device either not process the command or change the variable to closest possible value In any case the device will send back the value which is really set after proceeding the command 8 if a...

Page 12: ...en switch test broadcasting on otherwise the module would broadcast permanently and never be able to receive any other command When configuring battery powered modules always use the Wake On Radio WOR...

Page 13: ...ur version of MS Windows operating system failed in automatic installation of a driver for connected USB GateWay or USB IRDA device make an installation of ugw3 inf driver manually Connect the device...

Page 14: ...the instructions below 3 4 1 How to disable driver signature enforcement in Windows 8 system Enforcement of signed driver installation in Windows 8 can be disabled by following procedure by pressing...

Page 15: ...soft user login password Select Device in main menu of the user account page and click to Obtain BitLocker recovery key in Desktop section and Bitlocker subsection The new screen with recovery keys wi...

Page 16: ...Interbyte timeout 50 ms TX On timeout 200 usec TX Off timeout 500 usec Run test 0 DEBUG 0 sysmon List of all configuration commands HELP can be displayed by entering of command into the command line a...

Page 17: ...diagnostics the function will be switched off anyway If the parameter should be changed permanently there is necessary to save the configuration to FLASH memory Configuration can be erased from the F...

Page 18: ...ring of one of following pre defined symbols flags value without flag none of below mentioned functions is involved value e setting of basic repeating mode without back transfer suppression hodnota Z...

Page 19: ...dules This setting is recommended in this case when the module works in the environment with permanent disturbance of carrier frequency and it has no sense to waste time and battery power by waiting f...

Page 20: ...dr setting of superordinate master address Master s address ma addr setting of alarm messages address Alarm address The module can be designated as a master of virtual bus by using of f command with m...

Page 21: ...0 baud value sysmon b 9600 IMPORTANT NOTE technically it is possible to set data bus transfer speed up to 115 200 baud value How ever according to the M Bus specification the maximum transfer speed of...

Page 22: ...not use Only for factory setting l slots number of transmitting timeslots Do not use Only for factory setting t timeout length of transmitting timeslot Do not use Only for factory setting D number deb...

Page 23: ...LP H module that can be set only via radio is module System Time However this setting is not required for any common application of the module The module can be synchronized with real time by using o...

Page 24: ...verview of WM868 MS LP H module configuration parameters Item Name Value Description Default 1 CONFIGURATION status configuration saving status read only 2 Address code module unique WACO RF address r...

Page 25: ...d a type of respective application port number Payload data coding method is determined by application type WACO SLRF data packet structure is shown in the figure 20 Figure 20 Structure of WACO system...

Page 26: ...the connected antenna cable will not stress the antenna connector of the device by tension or twist Excessive loads can damage or destroy antenna connectors The module is specified for installation in...

Page 27: ...gnaling cables to the module see paragraph 4 1 1 Risk of mechanical damage It is necessary to keep the sufficient space for the connecting of configuration cable as well when selecting a site for the...

Page 28: ...hort circuit by insulation of live ends of wires or by removal of useless power branches and connect the power supply again After dismantling label the module properly as dismounted and fill in the ap...

Page 29: ...eakdown of the device Correctness of power supplying can be checked by this procedure check if there is no electricity breakdown in the building check if the power supply is on and properly working ch...

Page 30: ...hooting of the malfunctioning in following steps visually check surrounding of the installation site to find out if there are any changes that can influence radio signal e g new objects things machine...

Page 31: ...base If the correctness of the identification is positively checked proceed with troubleshooting of the data bus communication malfunctioning in following steps visually check whether the bus cable fr...

Page 32: ...device is very likely caused by external circumstances especially installation environment mechanical damage excessive humidity overvoltage of power supplying or voltage pulses induced to the module...

Reviews: