3.5
Setting of WM868-MS-LP-H module parameters by configuration cable
In following part of the document there is a description of these parameters of the WM868-MS-LP-H module, that
can be displayed and examined from PC connected to the module by configuration cable. Some of the parameters
can be changed by configuration commands entered
”
from the console” as described in paragraph
3.5.1
List of WM868-MS-LP-H module configuration parameters and commands
List of all configuration parameters of the module can be displayed by entering of
”/“
(slash) command and pressing
of
”
ENTER” key. The following list of parameters will display in the terminal window:
sysmon>/
CONFIGURATION: OK
Address: 0xFFFEDFE2
Master: 0xFFFFFA39
Alarm: 0xFFFFFA39
Group: 0
Flags: C
PA table: C2
Channel: 0
Timeslot: 20 ms
# of timeslots: 5
Hop Count: 3
Test timeout: 1000 ms
Baud: 9600
8N1
Interbyte timeout: 50 ms
TX On
timeout: 200 usec.
TX Off
timeout: 500 usec.
Run test: 0
DEBUG: 0
sysmon>
List of all configuration commands (”HELP”) can be displayed by entering of
”/?”
command into the command
line and pressing of
”
ENTER” key. The following list of commands will display in the terminal window:
sysmon>/?
/W - save configuration
/# - clear configuration
/m addr
- set Master’s address
/ma addr - set Alarm address
/g group - set group (multicast address)
/h count - set hop count
/f [+-][emCwzG] - set flags (e-range extender, m-master, C-Carrier Detect
w-WOR mode, z-Zone Extender Algorithm, G- high gain)
/c number - set RF channel 0..2
/l slots - set # of timeslots in RF network
/t timeout - set timeslot timeout in ms
/P patable - set PA table value
/T timeout - set test timeout in ms
/E flag - run test (0-Off,1-On)
/D flag - debug (0-Off,1-On)
/b baud
set baud rate (300..115200)
/p [n|e|o]
set parity (none,even,odd)
/d number
set data bits (7,8)
/s number
set stop bits (1,2)
/i timeout
set interbyte timeout in ms
/O timeout
set TX On timeout in usec.
/F timeout
set TX Off timeout in usec.
/x - RESET
sysmon>
WM868-MS-LP-H