SOFTLINK WACO WM868 Manual Download Page 12

in case the variable has an index, put the index number in (information box

Has Index“ is ticked and

Index“

box is editable);

set up required value of the variable into the

Value“ field. If the variable will be just read (checked its current

value), leave the field blank. Those variables, that have

Read only“ status (invariable constants, measured

values) will have the

Value” box uneditable;

by clicking on

Add“ button add a variable to the sequence of variables used for configuration.

Entering of a variable into the

Variables” window is depicted in the right part of the figure

10

.

Command

GET

(reading the current variable value),

SET

(setting up the required variable value), or

WALK

(reading the current status of all variables) will be done only for one chosen device from the list of devices in

RF

Address“

tab. Run the required command by clicking on relevant button in the top of the screen. After the click,

there will appear an information window in which a progress of getting/setting process of will be displayed. As the
individual settings are performed, the

tick” symbols in the

Done” box appear item-by-item. The

Getting/Setting”

window will disappear after the all commands of the sequence are being accomplished, or after the expiration of
the preset time limit (TimeOut). The current variable values are listed in the field

Value” in the relevant row.

Figure 11: Progress of getting values of preselected variables of the module by using of

GET” command

To avoid serious mistakes that can bring the module into paralyzed condition, numb for further communication, it
is necessary to know the meaning of all modified variables of the device, including their mutual relations.

Example:

If value of

SLRF Test Flag” variable is set to ”1”, the module will be preset to send test messages in

period which is set up by variable

SLRF Test Timeout [ms]”. In this case the period is just 1 millisecond. The

trouble will occur if the test broadcasting would be switch on. It is necessary to set some reasonable period (e.g.
5 second) first and just then switch test broadcasting ”on”, otherwise the module would broadcast permanently and
never be able to receive any other command.

When configuring battery powered modules, always use the

Wake-On-Radio” (WOR) function. The function

enables to

wake up” the module with a special

waking” radio signal from

hibernation” mode (that means the

mode in which the module is almost permanently) to the mode of active signal reception. Keep in mind that by

waking up” of the particular required module the other modules, that are placed within the GateWay current

radio range, will also be activated. Excessive activating of the module can cause the reduction of its battery life. To
avoid the excessive

waking” of many modules around the GateWay it is recommended to follow these instructions:

- do not change the parameters if it is not necessary for the module’s functionality;

- consider the succession

of the configuration commands (or prepare them as a

template”);

- do not use command

WALK” if not

necessary - (reading of all module variables);

- find suitable place for the configuration, that is in a good reach

of configured device.

We also recommend keeping the modules in closed boxes, shielded with aluminum foil (or in metal boxes) so the
modules are protected from the excessive

waking up” and their batteries won’t be damaged. When you do the

preliminary configuration before mounting, always take out from the shielded box only the necessary number of
modules. After their configuration, the modules should be placed back in the shielded box.

3.3

USB-CMOS converter driver installation

If the computer operation system failed in automatic installing of the driver for the

USB-CMOS”, it is necessary

to install the driver manually. The relevant current driver can be found on a chip manufacturer’s (FTDI) webpages,
namely in the

VCP Drivers“ (Virtual COM Ports) section.

www.ftdichip.com/Drivers/VCP.htm

In the

Currently Supported VCP Drivers” table find a link to a driver relevant to your operating system. To

download the file, click on a link in the table. After downloading the file (in .ZIP format) into any directory in
your computer, unzip the file. It will create a new folder (directory) with a set of files (e.g.

CDM 2.08.24 WHQL

Certified”).

WM868-MS-LP-H

9

Summary of Contents for WACO WM868

Page 1: ...WIRELESS COMMUNICATION SYSTEM WACO WM868 WM868 MS LP H Revision 3 0 SOFTLINK s r o Tomkova 409 278 01 Kralupy nad Vltavou Czech Republic Phone 420 315707111 e mail sales softlink cz www softlink cz...

Page 2: ...List of WM868 MS LP H module configuration parameters and commands 13 3 5 2 Configuration group of commands for writing of configuration and reset 14 3 5 3 Commands for settings of radio frequency su...

Page 3: ...O USB GateWay in the MS Windows Device Manager 7 10 Entering of devices and variables into the remote configuration window 8 11 Progress of getting values of preselected variables of the module by usi...

Page 4: ...ctionality description below the WM868 MS LP H module can be used in applications of M Bus RS 485 data bus systems that are commonly deployed in industrial automation as well as in the area of remote...

Page 5: ...ower supply 24V DC For connecting of the power supply there is a screw on terminal with marked voltage polarity Power supplying must follow all the safety requirements according to the appropriate sta...

Page 6: ...ssion speed 300 9600 Baud Operation mode asynchronous Transmission parameters default 8 data bits 1 stop bit none parity Signal level by EN1434 3 EN60870 Nominal current consumption 1 5 mA Power suppl...

Page 7: ...nel 3 1 1 Connecting of module to computer Configuration can be performed by using of common USB port of the computer For the interconnection with a USB port of computer it is necessary to use an manu...

Page 8: ...unication choose Serial option of the connection type in the Session tab Check or set up the communication speed Speed to 19200 bits s and then enter into the Serial line tab the number of the serial...

Page 9: ...entation otherwise you would be risking the unwanted command enter that might be the same as the ones used for manufacturer settings diagnostics or service and repair 3 2 Configuration of the module v...

Page 10: ...th analyzer but it is connected to the remote Ethernet IP port of the IP network Internet anywhere over the world provided that there is an IP connection between the computer and the GateWay see figur...

Page 11: ...then the device either not process the command or change the variable to closest possible value In any case the device will send back the value which is really set after proceeding the command 8 if a...

Page 12: ...en switch test broadcasting on otherwise the module would broadcast permanently and never be able to receive any other command When configuring battery powered modules always use the Wake On Radio WOR...

Page 13: ...ur version of MS Windows operating system failed in automatic installation of a driver for connected USB GateWay or USB IRDA device make an installation of ugw3 inf driver manually Connect the device...

Page 14: ...the instructions below 3 4 1 How to disable driver signature enforcement in Windows 8 system Enforcement of signed driver installation in Windows 8 can be disabled by following procedure by pressing...

Page 15: ...soft user login password Select Device in main menu of the user account page and click to Obtain BitLocker recovery key in Desktop section and Bitlocker subsection The new screen with recovery keys wi...

Page 16: ...Interbyte timeout 50 ms TX On timeout 200 usec TX Off timeout 500 usec Run test 0 DEBUG 0 sysmon List of all configuration commands HELP can be displayed by entering of command into the command line a...

Page 17: ...diagnostics the function will be switched off anyway If the parameter should be changed permanently there is necessary to save the configuration to FLASH memory Configuration can be erased from the F...

Page 18: ...ring of one of following pre defined symbols flags value without flag none of below mentioned functions is involved value e setting of basic repeating mode without back transfer suppression hodnota Z...

Page 19: ...dules This setting is recommended in this case when the module works in the environment with permanent disturbance of carrier frequency and it has no sense to waste time and battery power by waiting f...

Page 20: ...dr setting of superordinate master address Master s address ma addr setting of alarm messages address Alarm address The module can be designated as a master of virtual bus by using of f command with m...

Page 21: ...0 baud value sysmon b 9600 IMPORTANT NOTE technically it is possible to set data bus transfer speed up to 115 200 baud value How ever according to the M Bus specification the maximum transfer speed of...

Page 22: ...not use Only for factory setting l slots number of transmitting timeslots Do not use Only for factory setting t timeout length of transmitting timeslot Do not use Only for factory setting D number deb...

Page 23: ...LP H module that can be set only via radio is module System Time However this setting is not required for any common application of the module The module can be synchronized with real time by using o...

Page 24: ...verview of WM868 MS LP H module configuration parameters Item Name Value Description Default 1 CONFIGURATION status configuration saving status read only 2 Address code module unique WACO RF address r...

Page 25: ...d a type of respective application port number Payload data coding method is determined by application type WACO SLRF data packet structure is shown in the figure 20 Figure 20 Structure of WACO system...

Page 26: ...the connected antenna cable will not stress the antenna connector of the device by tension or twist Excessive loads can damage or destroy antenna connectors The module is specified for installation in...

Page 27: ...gnaling cables to the module see paragraph 4 1 1 Risk of mechanical damage It is necessary to keep the sufficient space for the connecting of configuration cable as well when selecting a site for the...

Page 28: ...hort circuit by insulation of live ends of wires or by removal of useless power branches and connect the power supply again After dismantling label the module properly as dismounted and fill in the ap...

Page 29: ...eakdown of the device Correctness of power supplying can be checked by this procedure check if there is no electricity breakdown in the building check if the power supply is on and properly working ch...

Page 30: ...hooting of the malfunctioning in following steps visually check surrounding of the installation site to find out if there are any changes that can influence radio signal e g new objects things machine...

Page 31: ...base If the correctness of the identification is positively checked proceed with troubleshooting of the data bus communication malfunctioning in following steps visually check whether the bus cable fr...

Page 32: ...device is very likely caused by external circumstances especially installation environment mechanical damage excessive humidity overvoltage of power supplying or voltage pulses induced to the module...

Reviews: