SIRCO MOT PV - 543 544 B - SOCOMEC

5.2.3. fixed outputs - dry contacts

5.2.3.1. Description

As standard, the SIRCO MOT PV is equipped with four fixed outputs located on 
the motorisation module.

(Dry contacts to be powered by the user).

1

2

3

4

   

 

5

 

  

6

75A413 

200A 

Ue 750V 

19PV3020 

 

TRI

75A414 

250A 

Ue 750V 

19PV3025 

 

TRI

75A415 

400A 

Ue 750V 

19PV3040 

 

TRI

75A416 

500A 

Ue 750V 

19PV3050 

 

TRI

75A417 

630A  

Ue 750V 

19PV3063 

 

TRI

75A425 

200A  

Ue 1000V 

19PV4020 

 

TETRA

75A426 

250A  

Ue 1000V 

19PV4025 

 

TETRA

75A427 

400A  

Ue 1000V 

19PV4040 

 

TETRA

75A428 

500A   

Ue 1000V 

19PV4050 

 

TETRA

75A429 

630A   

Ue 1000V 

19PV4063 

 

TETRA

75A430 

I800A   

Ue 1000V 

19PV4080 

 

TETRA

75A431 

1000A   

Ue 1000V 

19PV4100 

 

TETRA

75A432 

1250A   

Ue 1000V 

19PV4120 

 

TETRA

75A433 

1600A   

Ue 1000V 

19PV4160 

 

TETRA

75A434 

2000A   

Ue 1000V 

19PV4200 

 

TETRA

75A436 

3200A   

Ue 1000V 

19PV4320 

 

TETRA

5.2.3.2. Position auxiliary contact

The SIRCO MOT PV is equipped with integrated position (I – O) auxiliary contact outputs through 3 off micro switches.

pins 13, 04, 24

(Normally Open contacts with pin 13 as common)

5.2.3.3. SIRCO MOT PV Product available output (motorisation)

 pin 63a – 64a 

(Normally Open contact that is held closed when the motorisation is available). 
This contact gives constant feedback about the product’s availability and it’s capacity to operate.

The SIRCO MOT PV performs a self diagnostics test on the motorisation module at startup, when put from Manual 
-> Auto and then every 5 minutes. This test ensures that the SIRCO MOT PV is operational in terms of control inputs. 
Should one of the tests fail, a second test is performed to reconfirm the error state. Should the SIRCO MOT PV 
motorisation module become unavailable, contact 63A – 64A are opened, the power/ready LED’s are switched off, 
and the fault LED is activated. The fault LED will remain active for as long as sufficient power is available and the fault 
condition is not reset. The fault is reset when the product is switched from AUT -> Manual -> Auto mode. 

SIRCO  MOT  PV  (Motorisation)  Product  Available  /  Unavailable  Watchdog  relay  will  open  for  any  of  the  following 
reasons  below:  For  added  security,  “Product  Availability”  is  informative  and  does  not  necessarily  inhibit  motor 
operation.

ProductUnavWarningLEDCondition:

inhibition

Product in manual mode

Yes

Motor not detected (Autotest)

No

Control voltage out of range

Yes

Operating factor fault active (N° of operations / min)

Yes

Powerfail active

Yes

Customer input autotest failed

No

Invalid product customisation

No

Abnormal switching when not in manual mode

Yes

Requested position not reached

Yes

Locked mode active when not in manual mode

Yes

External Fault -> User input

No

Unexpected current flowing through the motor when idle

Yes

Sampling rate for the above is every 10 ms
Exception: motor detection sampling rate is every 5 min

Summary of Contents for SIRCO MOT PV

Page 1: ...www socomec com SIRCO MOT PV Motorised photovoltaic switches EN Instruction Manual...

Page 2: ...rame B4 to B5 250 A to 800 A 11 3 1 2 Dimensions Frame B6 B7 1000 A to 2000 A 12 3 1 3 Dimensions Frame B8 3200 A 13 3 2 Copper bar connection for SIRCO MOT PV 3200 A 14 3 3 Mounting orientation 14 3...

Page 3: ...in French and English 4 4 1 Typical SIRCO MOT PV wiring 22 4 4 2 SIRCO MOT PV input and output contacts 23 5 OPERATING MODES 24 5 1 Manual operation 25 5 1 1 Emergency manual operation 25 5 1 2 Padlo...

Page 4: ...4 EN SIRCO MOT PV 543 544 B SOCOMEC...

Page 5: ...may be present on the product directly through the mains or indirectly through external circuits Voltages associated with this product may cause injury electric shock burns or death Prior to carry out...

Page 6: ...ication Power SIRCO MOT PV control voltage input within specified range 9 Auto Manual mode selector switch 10 Emergency manual operation Direct Handle 11 Red LED Indication Product Unavailable Manual...

Page 7: ...incoming and outgoing wiring details 2 Complete SIRCO MOT PV product current rating and reference number label serial number barcode and CE marking 3 Emergency manual operation direction of rotation...

Page 8: ...Temperature From 20 to 40 C without derating From 20 to 70 C when applying a Kt derating correction factor Kt Correction Factor Temperature 0 9 40 C 50 C 0 8 50 C 60 C 0 7 60 C 70 C Simplified deratin...

Page 9: ...Size Rating N of Poles Reference Number Weight kg Volume cm inc Packing Net Gross B4 250 A 4 19PV 4025 400 A 4 19PV 4038 B5 400 A 4 19PV 4039 400 A 4 19PV 4040 630 A 4 19PV 4063 800 A 4 19PV 4080 B6...

Page 10: ...ing protection against direct contact with the connection terminals or parts DOOR ESCUTCHEON PLATE An accessory to be fixed onto a cabinet door to frame the motor part of flush mounted SIRCO MOT PV sw...

Page 11: ...ng cutout dimensions for front door 6 Emergency removable handle CAUTION To consider the space required for manual operation and wiring When using the SIRCO MOT PV emergency handle Rating A Overall di...

Page 12: ...cy manual operation Maximum operating radius with an operating angle of 90 3 Terminal screens 4 Phase Barriers 5 Flush mounting cutout dimensions for front door 6 Emergency removable handle CAUTION To...

Page 13: ...45 45 90 12 5 1 Padlocking Facility Locking bracket for up to 3 padlocks of dia 4 8mm 2 Emergency manual operation Maximum operating radius with an operating angle of 90 3 Terminal screens 4 Phase Ba...

Page 14: ...n for SIRCO MOT PV 3200 A 129 155 74 37 129 155 74 37 129 155 74 37 129 155 74 37 3 3 Mounting orientation 250 A to 800 A Recommended OK Not Allowed OK 1000 A to 3200 A Recommended Not Allowed OK OK C...

Page 15: ...6 8 6 x 12 x 6 x 02 2500 A 2 x 100 x 10 H M12 55 6 8 3 x 6 x 3 x 03 2500 A 2 x 100 x 10 H M12 55 6 8 5 x 10 x 5 x 04 3200 A 3 x 100 x 10 H M12 35 6 8 3 x 3 x 05 3200 A 3 x 100 x 10 H M12 45 6 8 3 x 6...

Page 16: ...543 544 B SOCOMEC 3 4 2 Terminal shrouds Available from 250 A to 800 A Upstream or downstream mounting 250A B4 to 800A B5 Not compatible with bridging bars and phase barriers 3 4 3 Terminal screens 2...

Page 17: ...17 EN SIRCO MOT PV 543 544 B SOCOMEC 400A B5 to 2000A B7 3200A B8 3 4 4 Inter phase barriers O OFF...

Page 18: ...oltage applications that do not provide the availability of a neutral conductor Transformer data 400VAC 230VAC 200VA 301 302 230 Vac 12Vdc 301 302 230 Vac 400Vac 301 302 230 Vac 24Vdc DC power supply...

Page 19: ...e 0 position Optionally and when including the option padlocking in 2 positions key locking will be in positions I 0 250 A to 800 A 1000 A to 3200 A 3 5 2 Additional auxiliary contacts ntended for pre...

Page 20: ...A 1000 A 1250 A 1600A 2000 A 3200 A Frame size B4 B5 B6 B7 B8 Maximum cables section Cu mm2 120 240 240 2x185 2x240 2x240 2x240 6x185 Maximum bars width Cu mm 32 32 50 50 50 63 63 100 100 100 Tighten...

Page 21: ...atory 2P 2P Except 19PV 4039 2P 2P CHARGE LOAD CHARGE LOAD CHARGE LOAD CHARGE LOAD 3P 1P Except 19PV 4039 3P 1P CHARGE LOAD CHARGE LOAD CHARGE LOAD CHARGE LOAD Ie 400A per circuit ONLY 19PV 4039 Ie 80...

Page 22: ...A 16 x 11 60 28 5 15 75 15 75 28 5 15 svr_078_b_1_x_cat 1250 A 15 5 5 12 5 25 25 30 30 45 45 90 12 5 1600 A 3200 A 4 4 Control circuits 4 4 1 Typical SIRCO MOT PV wiring Example Control wiring for pho...

Page 23: ...9PV3020 3 TRI 75A414 250A Ue 750V 19PV3025 3 TRI 75A415 400A Ue 750V 19PV3040 3 TRI 75A416 500A Ue 750V 19PV3050 3 TRI 75A417 630A Ue 750V 19PV3063 3 TRI 75A425 200A Ue 1000V 19PV4020 4 TETRA 75A426 2...

Page 24: ...n AUT Mode AUTO Mode position is inhibited when padlocked or when the handle for manual operation is inserted into the SIRCO MOT PV MODE AUT 90 I 0 MANUAL MODE Not Padlocked Inhibits the control input...

Page 25: ...ffecting manual operation Ensure to remove the handle from the product before changing the selector switch back to AUT position 5 1 2 Padlocking The SIRCO MOT PV can be padlocked in the 0 position as...

Page 26: ...e 1000V 1 75A427 400A Ue 1000V 1 75A428 500A Ue 1000V 1 75A429 630A Ue 1000V 1 75A430 I800A Ue 1000V 1 75A431 1000A Ue 1000V 1 75A432 1250A Ue 1000V 1 75A433 1600A Ue 1000V 1 75A434 2000A Ue 1000V 1 7...

Page 27: ...simply bridging terminals 316 and 317 NOTE 313 317 closed Force SIRCO MOT PV to OFF Position takes priority over all other orders no matter of the control logic used Impulse logic standard configurati...

Page 28: ...e The SIRCO MOT PV performs a self diagnostics test on the motorisation module at startup when put from Manual Auto and then every 5 minutes This test ensures that the SIRCO MOT PV is operational in t...

Page 29: ...00000 cycles Response Time 5 10 ms Startup duration 200ms Rated Voltage Switching Voltage 250VAC Rated Current 5A Surge protection Vin_sg 4 8kV 1 2 50 s surge ESD withstand voltage Contact air 2 4kV D...

Page 30: ...to external order I O Verify the selected control logic wiring impulse or contactor Verify the connector connections The fault manuel LED is ON The FAULT MANUAL LED is on when in manual mode this is n...

Page 31: ...31 EN SIRCO MOT PV 543 544 B SOCOMEC...

Page 32: ...Non contractual document 2016 Socomec SAS All rights reserved www socomec com 543 544 B EN 09 16 CORPORATE HQ CONTACT SOCOMEC SAS 1 4 RUE DE WESTHOUSE 67235 BENFELD FRANCE...

Reviews: