2.3.7. eMC standard
The SIRCO MOT PV is designed and built in accordance with IEC 60947-1 standards
(Products intended to be installed in an «Industrial, Commercial and/or Residential Environment» therefore respecting
both Class A as well as Class B EMC requirements).
Description
Std (IEC)
Requirement (criteria)
Conducted
CISPR 11
Class B
Radiated
CISPR 11
Class B
ESD contact
61000-4-2
4KV (B)
ESD air
61000-4-2
8KV (B)
Electromagnetic field
61000-4-3
10V/m (A)
RF Conducted
61000-4-6
10V (A)
Burst
61000-4-4
2KV (A) power
1KV (A) control
Surge Common
61000-4-5
2KV (A)
Surge differential
61000-4-5
1KV (B)
2.4. SIRCO mOT PV
accessories aVailable
2.4.1. Customer fitted accessory
terminal shrouds (250 to 800 a)
Incoming and outgoing protection against direct contact with
the connection terminals or parts.
Can be mounted top or bottom
.
terminal screens
Incoming and outgoing protection against direct contact with
the connection terminals or parts.
door escutcheon plate
An accessory to be fixed onto a cabinet door to frame the
motor part of flush mounted SIRCO MOT PV switches.
control Voltage transformer
Allows a standard 230 V AC device to be supplied with
400 VAC.
mounting spacers (250 to 800 a)
Raises the device’s terminals 10 mm away from the
backplate or frame.
others:
Refer to the end of this instruction manual or the latest
SOCOMEC product catalogue.
(Downloadable from
www.socomec.com
)
2.4.2. Factory fitted accessory
supplementary auXiliary contact (ac)
Pre-breaking and signaling of positions I : 1 additional auxiliary
contact NO / NC can be mounted.
Included as standard
for ratings from 3200A
.
For Low level AC: please consult
SOCOMEC.
ronis Key padlocKing
Locking of the electrical and manual operation by means of
a RONIS EL11AP lock. Possibility of locking in all positions, if
the “Padlocking in the 2 positions” option is ordered.
Not compatible with flush mounting.
padlocKing in 2 positions
Allows locking of the operation in the 2 positions I and 0.