5.1. Manual operation
5.1.1. emergency manual operation
The SIRCO MOT PV can be manually operated whilst retaining the electrical characteristics and performance of the
power switching function. This function is usually used in case of emergencies or during maintenance.
To operate the SIRCO MOT PV manually ensure that no live parts are accessible, turn the front selector switch into
the manual position and insert the handle into the emergency handle shaft location hole provided.
Turn the handle 90° clockwise or anti-clockwise (depending on the position to be reached) for each consecutive
change in position. I -> O -> I.
90°
I
0
CautIOn
Ensure to verify the product position and
direction of rotation before effecting manual
operation.
Ensure to remove the handle from the product
before changing the selector switch back to AUT
position.
5.1.2. Padlocking
The SIRCO MOT PV can be padlocked in the 0 position as standard whilst padlocking in positions I or O is available
as a factory fitted option.
To padlock the SIRCO MOT PV first ensure that the SIRCO MOT PV mode selector switch is on Manual then ensure
that the emergency manual operation handle is not inserted into the location hole. (Remove if inserted).
Pull the padlocking mechanism outwards to reveal the slot for inserting up to 3x dia. 4 - 8mm padlocks.
Padlock the device with approved quality padlocks of minimum diameter 4mm and maximum diameter of 8mm. A
maximum of 3x 8mm padlocks may be padlocked onto the SIRCO MOT PV to padlocking mechanism.
3x
Ø 4-8 mm
CautIOn
as standard, padlocking is only made possible in the “O position”, when in
manual mode and with the emergency handle not inserted.