69
EN
MASTERYS GP4 60-160 kVA - Ref.: IOMMASGPXX07-EN 05
15. TECHNICAL SPECIFICATIONS
Models
MASTERYS GP4
160 kVA
120 kVA
100 kVA
80 kVA
60 kVA
3/3
kVA
Input/Output phases
Electrical specifications - Input
3ph + N 400 Vac (-15/+20%) up to -40% @ 70% of nominal load
Vin
Mains voltage
Input frequency
40-70 ±10%
Hz
Input power factor
≥
0.99
Current distortion (THDi)
≤
2% (@: Pn, Resistive load, Mains THDv
≤
1%)
Electrical specifications - External battery
from +/- 200
V bat
Battery voltage range
(3)
up to +/- 330
(4)
Electrical specifications - Output
3Ph+N 380/400/415 V ±1%
V
Output voltage
(1)
50-60 Hz (selectable) ±0.01%
Hz
Output frequency
160
120
100
80
60
kVA
Nominal apparent power
160
120
100
80
60
kW
Nominal active power
Overload
(@ 25 °C; Vin > 380)
(2)
10 minutes
kW
200
150
125
100
75
240
180
150
120
90
1 minute
Crest factor
≥
2.7
Voltage distortion (THDv)
≤
1% (@: Pn, Resistive load)
≤
5% (@: Sn, non-linear load)
Electrical specifications - Bypass
Nominal output voltage ±15% (±20% if GENSET is used)
V
Bypass input voltage
50-60 ±2% selectable (±8% if GENSET is used)
Hz
Bypass input frequency
Environment
0-40 (15-25 recommended)
°C
Operating temperature
-5 to 50
°C
Storage temperature
up to 95% (condensation-free)
%
Relative humidity
1000 (without derating)
m
Max. altitude
< 57
< 55
< 53
dBA
Acoustic noise (@ 70% Pn)
Air cooling
Cooling type
m
Required cooling capacity
3
1440
1080
840
720
480
/h
Dissipated power max at Pn
nominal condition
8000
5940
4800
3950
2880
W
27297
20280
16388
13486
9833
BTU/h
Dissipated power max at Pn
worst condition
9350
6560
5500
4630
3360
W
31904
22397
18778
15807
11471
BTU/h
Standards
EN/IEC 62040-1, AS 62040-1
Safety
EN/IEC 62040-3, AS 62040-3
Type and performance
EN/IEC 62040-2, AS 62040-2
EMC
CE - IECEE CB Scheme
Product certification
RCM - EAC - CMIM
Product marks
Protective Class I
Protective class
< 1 mA
Touch current
IP20; IP21 (option)
Protection level