background image

8

EN

MODBUS RTU / MODBUS TCP for Modulys GP 2.0 - ITYS PRO UPS - Masterys GP4 UPS - Masterys BC+ UPS range - Ref.: IOMXXXOPXX00-EN  00

ITYS PRO

communication slots

Slot 1

Slot 2

RS232

(1)

Ethernet

1. MODBUS protocol is 

available through RS232, 
without the ADC+SL 
board. ADC+SL board 
has to be used for RS485 
serial link.
MODBUS TCP is available 
also through Ethernet 
Port.

MODULYS GP

communication slots

1. Only for service.

Slot 1

USB connector

(1)

Slot 2

Ethernet network

(1)

MASTERYS BC+ / GP4

communication slots

USB connector

(1)

Ethernet network

(1)

Slot 1

Slot 1

1.  Only for service.

Summary of Contents for ITYS PRO Series

Page 1: ...INSTALLATION AND OPERATING MANUAL www socomec com MODBUS RTU MODBUS TCP for Modulys GP 2 0 range ITYS PRO UPS range Masterys GP4 UPS range Masterys BC UPS range EN...

Page 2: ......

Page 3: ...1 UPS CONFIGURATION TABLE STARTING FROM 0X0001 26 7 2 UPS REFERENCE TABLE STARTING FROM 0X0010 27 7 3 UPS STATUS TABLE STARTING FROM 0X0030 27 7 4 ADDITIONAL UPS STATUS TABLE STARTING FROM 0X0034 29...

Page 4: ......

Page 5: ...S environment below manufacturer specified values for optimum operation UPS Operating Reference Standard Comply with safety requirements Read the UPS operating instructions carefully SOCOMEC retains t...

Page 6: ...nt provides information on the MODBUS protocol serial link or Ethernet network for MODULYS GP 2 0 ITYS PRO MASTERYS BC MASTERYS GP4 Before connecting monitoring equipment or a BMS system building mana...

Page 7: ...d to the com slots using 2 screws USING ADC SL OPTION This board includes RS485 insulated serial link and advanced dry input and output contacts Installation Slot 1 or slot 2 Screws for fixing Cabling...

Page 8: ...et 1 MODBUS protocol is available through RS232 without the ADC SL board ADC SL board has to be used for RS485 serial link MODBUS TCP is available also through Ethernet Port MODULYS GP communication s...

Page 9: ...nnection parameters are set by an auto baud rate procedure with a timeout of 40 seconds 4 3 Features and led description Standard supported IEEE 802 3 Mode supported 10 100Base T 10 100Mbps auto sensi...

Page 10: ...rallel system STATUS UPS STATUS Bits Read 0x0038 6 2 for parallel system ALARMS UPS ALARMS Bits Read 0x0040 80 MEASUREMENTS LIST OF VALUES Values Read 0x00C0 7 MEASUR CTRL MGNT BIT 1 MEAS MANAGED Bits...

Page 11: ...Unit data and module data Modular Unit view Subunit Module data access UNIT data access summary of module data 6 2 MODULE access data table mapping Table of access example UPS address UNIT address 0x...

Page 12: ...sition by default 0x0004 T003 Device number 1 to 15 1 0x0005 T004 Nominal kVA 10 if 0x000E 1 depends on the number of modules units 0x0006 T005 Nominal kW 10 if 0x000E 1 depends on the number of modul...

Page 13: ...ule 1 present b01 Module 2 present b02 Module 3 present b03 Module 4 present b04 Module 5 present b05 Module 6 present b06 Module 7 present b07 Module 8 present b08 b09 b10 b11 b12 b13 bypass module b...

Page 14: ...011 Operating DEVICE STATUS b12 S012 Available b13 S013 On Standby b14 S014 Isolated b15 S015 Maintenance Alert 0x0031 b00 S016 Output Breaker closed DEVICE ENVIRONMENT b01 S017 Maintenance Bypass clo...

Page 15: ...ion 0x0033 b00 S048 Rectifier Input Supply present RECTIFIER b01 S049 Rectifier ON b02 S050 Charger ON b03 S051 b04 S052 Inverter ON INVERTER b05 S053 Inverter Switch ON b06 S054 b07 S055 b08 S056 Byp...

Page 16: ...S078 Programmable S078 b15 S079 Programmable S079 0x0035 b00 S080 Programmable S080 CUSTOM IN OUT b01 S081 Programmable S081 b02 S082 Programmable S082 b03 S083 Programmable S083 b04 S084 Programmable...

Page 17: ...ES b01 S097 Module 2 Operating b02 S098 Module 3 Operating b03 S099 Module 4 Operating b04 S100 Module 5 Operating b05 S101 Module 6 Operating b06 S102 Module 7 Operating b07 S103 Module 8 Operating b...

Page 18: ...Service Alarm b14 A014 Remote Service Preventive Alarm b15 A015 General Alarm 0x0039 b00 A016 Battery disconnected BATTERY b01 A017 Battery discharged b02 A018 b03 A019 Operating on Battery b04 A020...

Page 19: ...A049 Bypass Preventive Alarm b02 A050 Bypass Input Supply not OK b03 A051 Phase Rotation fault b04 A052 Bypass Backfeed detection b05 A053 b06 A054 Fan failure b07 A055 ACS Alarm 1 ENVIRONMENT b08 A05...

Page 20: ...ogrammable A076 b13 A077 Programmable A077 b14 A078 Programmable A078 b15 A079 Programmable A079 0x003D b00 A080 Programmable A080 CUSTOM IN OUT b01 A081 Programmable A081 b02 A082 Programmable A082 b...

Page 21: ...MMARY b01 A097 Module 2 General Alarm b02 A098 Module 3 General Alarm b03 A099 Module 4 General Alarm b04 A100 Module 5 General Alarm b05 A101 Module 6 General Alarm b06 A102 Module 7 General Alarm b0...

Page 22: ...2 A 0x0048 M008 Output current L3 A 0x0049 M009 0x004A M010 Output voltage L1 V 0x004B M011 Output voltage L2 V 0x004C M012 Output voltage L3 V 0x004D M013 Output frequency Hz 0x004E M014 0x004F M015...

Page 23: ...L3 kVA 0x0073 M051 Output Active Power L1 kW 0x0074 M052 Output Active Power L2 kW 0x0075 M053 Output Active Power L3 kW 0x0076 M054 Output voltage U12 V 0x0077 M055 Output voltage U23 V 0x0078 M056...

Page 24: ...to 0 means that remote commands are not permitted Address Only for SYSTEM UPS view Bit Acronym Description Permission 0x00C9 b00 C000 Reserved 0x00C9 P000 b01 C001 P001 b02 C002 P002 b03 C003 P003 b0...

Page 25: ...CB to 0x00CE unsing as a Function the code 0x10 See Functions used and Summary of frame format paragraphs for Modbus frame description Generic address Acronym Description Value Remarks MSB LSB 0x00CB...

Page 26: ...002 T001 Number of devices in level 1 1 to 15 1 unit 0x0003 T002 Position of devices present 1 1 first position by default 0x0004 T003 Device number 1 to 15 1 0x0005 T004 Nominal kVA 10 if 0x000E 1 0x...

Page 27: ...arting from 0x0030 ITYS PRO STATUS Generic ad dress Bits Acronym Description 0x0030 b00 S000 Load protected by Inverter OUTPUT STATUS b01 S001 b02 S002 Load supplied by automatic Bypass b03 S003 b04 S...

Page 28: ...b05 S037 Battery Test interrupted b06 S038 Floating Voltage reduced b07 S039 b08 S040 DC STORAGE SYSTEM b09 S041 b10 S042 b11 S043 b12 S044 b13 S045 b14 S046 b15 S047 0x0033 b00 S048 Rectifier Input S...

Page 29: ...Programmable S078 b15 S079 Programmable S079 0x0035 b00 S080 Programmable S080 CUSTOM IN OUT b01 S081 Programmable S081 b02 S082 Programmable S082 b03 S083 Programmable S083 b04 S084 Programmable S084...

Page 30: ...15 General Alarm 0x0039 b00 A016 Battery disconnected BATTERY b01 A017 Battery discharged b02 A018 End of Backup Time b03 A019 Operating on Battery b04 A020 Battery Temperature Alarm b05 A021 Battery...

Page 31: ...48 Bypass Critical Alarm BYPASS b01 A049 Bypass Preventive Alarm b02 A050 Bypass Input Supply not OK b03 A051 Phase Rotation fault b04 A052 b05 A053 Transformer Alarm b06 A054 Fan failure b07 A055 ACS...

Page 32: ...rammable A076 b13 A077 Programmable A077 b14 A078 Programmable A078 b15 A079 Programmable A079 0x003D b00 A080 Programmable A080 CUSTOM IN OUT b01 A081 Programmable A081 b02 A082 Programmable A082 b03...

Page 33: ...Output voltage L1 V 0x004B M011 Output voltage L2 V 0x004C M012 Output voltage L3 V 0x004D M013 Output frequency Hz 0x004E M014 0x004F M015 Ambient Temperature C 0x0050 M016 Battery voltage string V B...

Page 34: ...4 M052 Output Active Power L2 kW 0x0075 M053 Output Active Power L3 kW 0x0076 M054 Output voltage U12 V 0x0077 M055 Output voltage U23 V 0x0078 M056 Output voltage U31 V 0x0079 M057 0x007A M058 0x007B...

Page 35: ...means that remote commands are not permitted Address Only for SYSTEM UPS view Bit Acronym Description Permission 0x00C7 b00 C000 Reserved 0x00C9 P000 b01 C001 P001 b02 C002 P002 b03 C003 P003 b04 C004...

Page 36: ...ress using as a Function the code 0x10 See Functions used and Summary of frame format paragraphs for Modbus frame description Generic address Acronym Description Value Comments MSB LSB 0x00CB K000 Min...

Page 37: ...range Ref IOMXXXOPXX00 EN 00 8 MODBUS TABLE MASTERYS BC GP4 8 1 UPS architecture Masterys unit Masterys parallel system UNIT UNIT 1 SYSTEM UNIT 2 8 2 Unit access data table mapping 0x0000 or 0x1000 fo...

Page 38: ...ices present each unit present is set by a bit If unit 1 present b00 1 1 first position by default 0x0004 T003 Device number 1 to 8 1 o 8 0x0005 T004 Nominal kVA 10 if 0x000E 1 depends on the number o...

Page 39: ...Description Value Remarks Length Number of ASCII char 0x0010 I000 SERIAL NUMBER 10 20 MSB first char of string 0x001A I001 SOCOMEC REFERENCE 10 20 MSB first char of string 0x0024 I002 USER DEVICE REF...

Page 40: ...Available b13 S013 On Standby b14 S014 Isolated b15 S015 Maintenance Alert 0x0031 b00 S016 Output Breaker closed DEVICE ENVIRONMENT b01 S017 External maintenance bypass close 1 b02 S018 b03 S019 b04...

Page 41: ...ption 0x0033 b00 S048 Rectifier Input Supply present RECTIFIER b01 S049 Rectifier ON b02 S050 Charger ON b03 S051 b04 S052 Inverter ON INVERTER b05 S053 Inverter Switch ON b06 S054 b07 S055 b08 S056 B...

Page 42: ...S077 b14 S078 Programmable S078 b15 S079 Programmable S079 0x0035 b00 S080 Programmable S080 CUSTOM IN OUT b01 S081 Programmable S081 b02 S082 Programmable S082 b03 S083 Programmable S083 b04 S084 Pro...

Page 43: ...perating b01 S097 Unit 2 Operating b02 S098 Unit 3 Operating b03 S099 Unit 4 Operating b04 S100 Unit 5 Operating b05 S101 Unit 6 Operating b06 S102 Unit 7 Operating b07 S103 Unit 8 Operating b08 S104...

Page 44: ...ice Preventive Alarm b15 A015 General Alarm 0x0039 b00 A016 Battery disconnected BATTERY b01 A017 Battery discharged b02 A018 b03 A019 Operating on Battery b04 A020 Battery Temperature Alarm b05 A021...

Page 45: ...050 Bypass Input Supply not OK b03 A051 Phase Rotation fault b04 A052 Bypass Backfeed detection b05 A053 Transformer Alarm b06 A054 Fan failure b07 A055 ACS Alarm 1 ENVIRONMENT b08 A056 Maintenance By...

Page 46: ...A076 Programmable A076 b13 A077 Programmable A077 b14 A078 Programmable A078 b15 A079 Programmable A079 0x003D b00 A080 Programmable A080 CUSTOM IN OUT b01 A081 Programmable A081 b02 A082 Programmabl...

Page 47: ...3 A099 Unit 4 General Alarm b04 A100 Unit 5 General Alarm b05 A101 Unit 6 General Alarm b06 A102 Unit 7 General Alarm b07 A103 Unit 8 General Alarm b08 A104 b09 A105 b10 A106 b11 A107 b12 A108 b13 A10...

Page 48: ...47 M007 Output current L2 A 0x0048 M008 Output current L3 A 0x0049 M009 0x004A M010 Output voltage L1 V 0x004B M011 Output voltage L2 V 0x004C M012 Output voltage L3 V 0x004D M013 Output frequency Hz...

Page 49: ...0x0070 M048 Output Apparent P L1 kVA OUTPUT DETAIL 0x00C3 0x0071 M049 Output Apparent P L2 kVA 0x0072 M050 Output Apparent P L3 kVA 0x0073 M051 Output Active Power L1 kW 0x0074 M052 Output Active Pow...

Page 50: ...ly for SYSTEM UPS view Bit Acronym Description Permission 0x00C9 b00 C000 Reserved 0x00C7 P000 b01 C001 P001 b02 C002 P002 b03 C003 P003 b04 C004 P004 b05 C005 P005 b06 C006 P006 b07 C007 P007 b08 C00...

Page 51: ...used and Summary of frame format paragraphs for Modbus frame description Generic address Acronym Description Value Remarks MSB LSB 0x00CB K000 Minutes Seconds Minute 0 59 Seconds 0 59 read write 0x00...

Page 52: ...ytes Data CRC 1 0x03 2 nb of words MSB LSB MSB LSB Values Computed Function 0x06 bytes frame description Slave Function Address Data CRC 1 0x06 MSB LSB MSB LSB MSB LSB By default MODBUS TABLE Value to...

Page 53: ...he starting address nb of words table length SUBUNIT UNIT not present 0x86 0x01 Bad function Data in read only area Data reserved 0x86 0x02 Bad address Bad address event 0x90 0x01 Bad function Data in...

Page 54: ...DBUS RTU MODBUS TCP for Modulys GP 2 0 ITYS PRO UPS Masterys GP4 UPS Masterys BC UPS range Ref IOMXXXOPXX00 EN 00 10 APPENDIX 1 INTERFACE CONFIGURATION USING DIGI DEVICE DISCOVERY Discovery tools IP s...

Page 55: ...MODBUS RTU MODBUS TCP for Modulys GP 2 0 ITYS PRO UPS Masterys GP4 UPS Masterys BC UPS range Ref IOMXXXOPXX00 EN 00 Device configuration Password dbps Login root Firmware download in case of malfuncti...

Page 56: ...nds to the transaction number 0000 corresponds to the protocol identifier 0006 corresponds to the number of bytes length of the message Note the CRC is removed in the encapsulated MODBUS frame REPLY F...

Page 57: ......

Page 58: ......

Page 59: ......

Page 60: ...nce 80countries where our brand is distributed 8production sites q France x3 q Italy q Tunisia q India q China x2 27subsidiaries q TRSQ KH q DKFHTL q GHM q Q MBD q DQL MX q MCH q S KX q DSGDQK MCR q N...

Reviews: