13
EN
MODBUS RTU / MODBUS TCP for Modulys GP 2.0 - ITYS PRO UPS - Masterys GP4 UPS - Masterys BC+ UPS range - Ref.: IOMXXXOPXX00-EN 00
6.4 Unit con
fi
guration table, starting from 0x1000
Address
Acronym
Description
Value
Remarks
0x1001
T000
UPS installation code and
Device type
MSB = 8 for modular
lsb = 1 for Unit
0x1002
T001
Number of devices in level
-1
1 to 15
1 to 8 modules
0x1003
T002
Position of present
devices
b00
Module 1 present
b01
Module 2 present
b02
Module 3 present
b03
Module 4 present
b04
Module 5 present
b05
Module 6 present
b06
Module 7 present
b07
Module 8 present
b08
b09
b10
b11
b12
b13
bypass module
b14
b15
0x1004
T003
Device number
1 to 15
1 to 8
6.5 UPS reference table, starting from 0x0010
Address
Acronym
Description
Value
Remarks
Length
Number of ASCII char.
0x0010
I000
SERIAL NUMBER
10
20
MSB = first char of
string
0x001A
I001
SOCOMEC REFERENCE
10
20
MSB = first char of
string
0x0024
I002
USER DEVICE
REFERENCE
6
12
MSB = first char of
string
0x002A
I003
USER DEVICE
LOCATION
6
12
MSB = first char of
string