MODBUS RTU / MODBUS TCP for Modulys GP 2.0 - ITYS PRO UPS - Masterys GP4 UPS - Masterys BC+ UPS range - Ref.: IOMXXXOPXX00-EN 00
8.3 UPS con
fi
guration table, starting from 0x0001
NOTE!
Fields or bit fields not described must be considered as reserved/unused.
Address
Acronym
Description
Value
Default values
0x0001
T000
UPS installation code
and Device type
MSB = UPS
installation
Code (1 byte)
lsb = Device type (1 byte)
(0x01(0x01) unit
(0x06)(0x01) parallel
0x0002
T001
Number of devices in
level -1
1 to 8 (only for parallel system)
1 unit
0x0003
T002
Position of devices
present
each unit present is set by a bit.
If unit 1 present b00 = 1
1 first position by
default
0x0004
T003
Device number
1 to 8
1 o 8
0x0005
T004
Nominal kVA
*10 if 0x000E = 1
depends on the
number of units
0x0006
T005
Nominal kW
*10 if 0x000E = 1
depends on the
number of units
0x0007
T006
Phase number
MSB = Input
phases 1 – 3
LSB = Output phases 1 - 3
(0x03)(0x03)
0x0008
T007
Function
b00
eco mode enabled
b01
energy saver enabled
b02
b03
genset present
b04
b05
b06
b07
b08
0x0009
T008
Environment
b00
b01
b02
b03
b04
b05
b06
Without bypass
0x000A
T009
DC storage
b00
battery present
b01
0x000B
T010
Power share
0x000D
T012
free
free
0x000E
T013
measurements factor
0 = no factor / 1 = factor * 10
set to 1
0x000F
T014
Device reference
code
0x8200 = BC+
0x8300 = GP4