35
EN
MODBUS RTU / MODBUS TCP for Modulys GP 2.0 - ITYS PRO UPS - Masterys GP4 UPS - Masterys BC+ UPS range - Ref.: IOMXXXOPXX00-EN 00
7.8 COMMANDS table, starting from 0x00C7
To send a command bit, write to the 0x00C7 or 0x00C8 address using the function code '0x06'. See 'Functions
used' and 'Summary of frame format' paragraphs for Modbus frame description.
Each 0x00C7 or 0x00C8 bit defines a command to be executed by the UPS.
It is necessary to change the parameter 'REMOTE CONTROL' to 'enabled' on the mimic-panel to allow the
command to be received; then the related permission P000 switches to 1.
P000 set to 0 means that remote commands are not permitted.
Address
Only for SYSTEM/UPS view
Bit
Acronym
Description
Permission
0x00C7
b00
C000
Reserved
0x00C9
P000
b01
C001
P001
b02
C002
P002
b03
C003
P003
b04
C004
P004
b05
C005
P005
b06
C006
P006
b07
C007
P007
b08
C008
P008
b09
C009
P009
b10
C010
P010
b11
C011
P011
b12
C012
P012
b13
C013
P013
b14
C014
P014
b15
C015
P015
0x00C8
b00
C016
eco mode On
0x00CA
P016
b01
C017
eco mode Off
P017
b02
C018
P018
b03
C019
P019
b04
C020
P020
b05
C021
P021
b06
C022
P022
b07
C023
P023
b08
C024
P024
b09
C025
P025
b10
C026
P026
b11
C027
P027
b12
C028
Battery Test
P028
b13
C029
P029
b14
C030
P030
b15
C031
Reset Alarm
P031
Permission: 0x00C9 and 0x00CA
If the bit associated with commands is set to 1, this means the command is enabled by the UPS, and available to
run.