6
ITYS
10-20 kVA - Ref.: IOMITYTWXX0C-GB 00
2. INSTALLATION
2.1. SHIPPING AND MOVING
• The packaging guarantees the stability of the unit during shipping and physical transfer.
• The unit must remain in a vertical position during all shipping and moving operations.
• Ensure that the fl oor is strong enough to support the weight of the unit.
• Carry the packaged unit as close as possible to the installation site.
WARNING! HEAVY WEIGHT!
Move the unit using a forklift truck taking the utmost care at all times.
The unit MUST be handled by at least two people.
Do not move the unit by putting pressure on the front door.
When moving the unit on even slightly sloping surfaces, use the locking equipment and braking devices to ensure
that the unit does not fall over.
WARNING!
RISK OF ELECTRIC SHOCK!
When the equipment is transferred from a cold to a warm place wait approx. two hours after unpacking before
Installing the unit and putting it into operation.
CAUTION IF DAMAGED.
If the unit is found to be damaged externally or internally, or any of the accessories are damaged or missing,
contact SOCOMEC.
All packaging material must be recycled in compliance with the laws in force in the country where the system is
installed.
2.2. ENVIRONMENTAL
REQUIREMENTS
Install the unit in a technical room to which only skilled technicians have access. The room must be:
• of a suitable size;
• clean and dry;
• free from infl ammable items;
• maintained at a temperature between 0 and 40 °C.
The unit is not designed for outdoor use. Do not expose the unit to direct sunlight.
See TECHNICAL SPECIFICATIONS.