COUNTIS ECi
- Ref.: 538 470 A
TROUBLESHOOTING
• Device not switched on
Check the power supply cable.
110…400 Vac or 120…300 Vdc between terminals 20 and 22, if there is voltage present and the device
does not switch on, please return the device to us.
• Faulty communication
Check configuration in MANUAL mode: address, speed, parity, stop bit (p.12) and cabling (p.6).
For more information on the RS485 connection procedure, refer to the technical bulletin available on the
web site: www.socomec.fr
• The meter does not advance incrementally
Poor connection.
Go to the menu E. Digital. (p.11)
Connect the input to be tested to terminal
+ 51
(p.8) to verify that the "pulse detected" pictogram
changes state correctly.