12

COUNTIS ECi

 - Ref.: 538 470 A

PROGRAMMING

 Hold down for 

3 seconds.

The screens presented in the USAGE/PROGRAMMING charts are not all visible:  

their display depends on the version of your 

COUNTIS ECi 

and their configuration.

MANUAL mode

This mode enables manual configuration of all communication parameters JBUS/MODBUS: 

Address, Speed, Parity, Stop bit.

AUTO mode

This mode enables automatic configuration of most of the communication parameters (Speed, 

Parity, Stop bit).
Only the communication address for the COUNTIS has to be entered. The mode only functions 

under the following conditions:

 •  Communication speed between 9600 and 38400 baud.
 • JBUS/MODBUS frame format:
- 8 bits + 2 stop + no parity,
- 8 bits + 1 stop + parity.

*

Input 1 

Mode

Output

Src / Type / Delay

Inputs Cost

Currency

Ana In 1

Type / Unit

Com JBUS

Adress / Mode

Alarm 1

Mode / Sever

Date

Day / Month / Year

Language

English

Maintenance

Factory Cfg / Action

Pulse meter, logical 

status or deactivated

Logical output setting: 

source of control, NO/

NC type and time

Currency setting

Typical setting:

0/20mA, 4/20mA or 

deactivated and unit

Mode, address setting

Mode: logical,

analogue,  

combination or 

deactivated

Day, month, year 

setting

Language selection

Reset to factory 

settings

Input 1 

Type / Delay

NO/NC type and time

Input 1 

Unit / Weight

Input 1 

Enable / Cost

Ana In 1

Min / Max

Com JBUS

Baudrate/ Stop / Parity

Ana In 1

Synchro / Integ

Alarm 1

Src / Type

Heure

Hour / Minute / Second

Lock Code

1000

Display

Contr./ Backl./ Timeout

Maintenance

Input Reset / Src / Act

Pulse weight and unit

Currency  

conversion  

activation

Sensor setting

(mesurement range)

Speed, stop, parity 

setting

Sync source and 

integration time

Logical alarm setting: 

source and type

Hours, minutes, 

seconds setting

Password selection, 

used for modifying the 

config.

Contrast, brightness, 

standby setting

Input reset

Input 1 

Synchro / Integ

Sync source and 

integration time

Input 1 

Reset/ Partial/ Custom

Idem  

Ana In 

2

Alarm 1

Src1 / Src2 / Type

Alarm 1

Src / Type / Hyst

Alarm 1

Low / High

Idem 

 Alarm 2   >  

Alarm 5

Pulse metering reset

.

.

Setting of combination 

alarm: source 1, 

source 2 and type

Setting of analogue 

alarm: source, type 

and hysteresis

Setting of analogue 

alarm: low or high limit

.

Idem  

Input 2

  >  

Input 7

.

Idem  

Input 2

  >  

Input 7

Modification with 

code 6825

Modification with

code 1000

*

Summary of Contents for COUNTIS ECi2

Page 1: ...l un I Jet _________ __ Socomec Countis ECi2 Countis ECi3 https www uni jet com catalog sistemyi kommutaczii kontrolya i zashhityi schetchiki socomec countis ecix html...

Page 2: ...COUNTIS ECi2 ECi3 Operating instructions Multi utility pulse concentrator GB F D I NL E P...

Page 3: ...i Ref 538 470 A HAZARDS AND WARNING 3 INITIAL CHECKS 3 INTRODUCTION 4 JBUS MODBUS COMMUNICATION 6 INSTALLATION 7 CONFIGURATION 10 USE 11 PROGRAMMING 12 TECHNICAL CHARACTERISTICS 13 TROUBLESHOOTING 14...

Page 4: ...fore reconnecting this device to the power supply always use the appropriate specified voltage to supply this device Failure to comply with these precautions could result in serious injuries Risk of d...

Page 5: ...losed pulses present or not the physical and functional status of the logical output contact open or closed output active or inactive the status of 5 customisable events date activation time duration...

Page 6: ...ctionalities of the COUNTIS ECi2 It also has 2 analogue 0 4 20 mA inputs with the following functionalities Instantaneous relative and absolute in the chosen unit values with direct reading on the dis...

Page 7: ...ion interface over more than 1200 m For more information on the connection procedure refer to the technical bulletin available on the web site www socomec com Important It is essential to connect a re...

Page 8: ...meter can be mounted on a 35 mm rail EN 60715TH35 It must be used inside electrical cabinets 0 6 Nm 5 mm 0 14 2 5 mm2 0 14 2 5 mm2 0 6 Nm 8 mm 0 2 6 mm2 0 2 4 mm2 0 4 20mA R 120 RS485 Aux 110 400 Vac...

Page 9: ...UNTIS ECi Ref 538 470 A Connecting logical inputs Internal polarisation cable length 1000 m max 1 5 mm min External polarisation cable length 1000 m max 1 5 mm min DC AC Stabilized power supply 10 30...

Page 10: ...9 COUNTIS ECi Ref 538 470 A Connecting analogue inputs COUNTIS ECi3 version 0 4 20mA DC AC 0 4 20mA 0 4 20mA 0 4 20mA Passive sensor Active sensor Stabilized power supply Passive sensor Active sensor...

Page 11: ...rs can be modified EXCEPT those locked by the code 6825 Advanced user code 6825 not configurable allows access to all parameters accessible with the code 1000 as well as sensitive maintenance paramete...

Page 12: ...etting Input 1 Day Week Ana In 2 Rel Abs Daily and weekly metering Analogue input relative value and absolute value Input 1 Month Year Input 1 Dig Stat Phys Func Alarm 1 Date Duration Top Synchro Last...

Page 13: ...tting 0 20mA 4 20mA or deactivated and unit Mode address setting Mode logical analogue combination or deactivated Day month year setting Language selection Reset to factory settings Input 1 Type Delay...

Page 14: ...G IEC 60068 2 6 10 to 100Hz Dimensions 73x90x67 mm L x W x H Weight 215 g Protection index of enclosure IP51 IP20 Front Case Cat Install degree of pollution III 2 IEC 61010 1 ed 3 300Vac Ph N Display...

Page 15: ...us Faulty communication Check configuration in MANUAL mode address speed parity stop bit p 12 and cabling p 6 For more information on the RS485 connection procedure refer to the technical bulletin ava...

Page 16: ...vement H E A D O F F I C E SOCOMEC GROUP S A capital 11 302 300 R C Strasbourg 548500 149 B 1 Rue de Westhouse B P 60010 F 67235 Benfeld Cedex FRANCE I N T E R N A T I O N A L S A L E S D E P A R T M...