Programming
Controller
ATyS
OPERATION
ATyS C40
44
SOCOMEC - Réf. : 532 929 B
Presentation
Operational modes
Programming
Operation
Visualisation
Automatic sequences
• This mode allows product parameters configuration
• Always accessible in
mode (when programmed on
an input)
• Always accessible in AUT mode, changeover switch on
priority source, priority source being available
• Not accessible when “test off load”, “test on load”
functions are active or during automatic sequence.
Parameters requiring programming before
use:
• type of network
• nominal voltage
• nominal frequency
• control logic
• number of auxiliary contact.
>
Navigation in the menus
•
Parameters access:
Press “up”, “down”, “left” & “right” push buttons
•
Parameter modification:
press “left” & “right” push button to access the parameter to modify
Press “up’’ and “down” push buttons to modify the parameter
and “validate”
•
Return to main menu:
press “ESC” push button
Value is only modified after validation
+
or
+
>
Programming exit
• Press and hold for 5 s
“validation” push button
>
Programming access
•
Step 1:
press and hold for 5 s
“validation” push button
•
Step 2:
enter code (factory code = 1000)
using navigation push buttons
•
Step 3:
press validation
push button