Programming
Controller ATyS
OPERATION
51
SOCOMEC - Réf. : 532 929 B
>
Menu Timer
LCD
Denomination
Definition
Setting Default
range
values
Gen Failure
Timer source 1
Delays source 1 failure detection
Delay to transfer
timer source 1
0 Secours Timer
source 1 to
source 2
Cool down
timer source 1
Standby network stability validation before transfer source 1 ->
source 2
Rest in zero position (open position) when transferring from
source 1 to source 2
Allows generator cooling down period after load’s retransfer
from source 1 -> source 2
From 0 to 60 s
From 0 to 60 s
From 0 to 20 s
From 0 to
30 mn
5 s
5 s
0 s
4 mn
1
2
1
2
1
2
Gen Failure
Timer source 2
Delays source 2 failure detection
From 0 to 60 s
5 s
1
2
Delay to transfer
timer source 2
Standby network stability validation before transfer source 2 ->
source 1
From 0 to 60 s
5 s
1
2
0 Secours Timer
source 2 to
source 1
Rest in zero position (open position) when transferring from
source 2 to source 1
From 0 to 20 s
0 s
1
2
Cool down
timer source 2
Allows generator cooling down period after load’s retransfer
from source 2 -> source 1
From 0 to
30 mn
4 mn
1
2
1
2
1
2