Programming
Controller ATyS
OPERATION
49
SOCOMEC - Réf. : 532 214 C
Network
nominal
frequency
Network nominal frequency
50 Hz or 60 Hz
50 Hz
1
2
PARAMETERS CHARACTERISTICS
>
Menu Setup
LCD
Denomination
Definition
Setting
Default
range
values
* Refer to annexes.
(1) It might be necessary for some breakers not to set up OMR and OMF timers to 0. (2 sec.)
1
2
Type of
network*
Number of active conductors of controlled network
(refer to annexes)
1BL, 2BL,
2NBL, 3NBL,
4NBL, 41 NBL
4NBL
Network
nominal voltage
Phase-Neutral voltage for 1BL & 41NBL
Phase-Phase voltage for others
from 100 V
to 400 V
400 V
Network priority
selection
Manual
Retransfer
Activation of the feature
Keypad selection (1 or 2)
Also possible via external contact using option
1 or 2
(
or )
2
1
1
(
)
1
Programming
code
modification
Possible to change the programming code
from 0000 to
9999
Yes or No
1000
No
Number of
permutation
counter Reset
Allows
source ->
source automatic
sequences
counter reset
2
1
Yes or No
No
Type of control
logic selection
Impulse, contactor or breaker.
It might be necessary for some breakers not to set up
OMR and OMF timers to 0 (2 sec. for exemple).
Imp, con, brE
Imp
1
2
1
2
1
2
1
2
1
2
Genset start
signal state
Normally opened or closed
NO or NC
NO
1
2
1
2
Number of
auxiliary contact
Depending on the number if available auxiliary contacts
(switch, contactor, breaker)
0, 2, 3
2
1
2
Parameter 1,
return in
position 0
Allows to go to position 0 in case of voltage or frequency
outage (out if the defined U, f range)
Yes or No
No
1
2
Parameter 2
return in
position 0
Allows to go to position 0 in case of voltage or frequency
outage (out if the defined U, f range)
Yes or No
No
1
2
1
2