6. CONNECTION
6.1.
Connecting the COUNTIS E00/02
L
L
N
N
4 5
L
L’
40A
N
230 VAC 50/60 Hz
-+
Solid / Stranded
1.5 mm
2
-> 6 mm
2
0.47 in
/ 12 mm
PZ2
13.28 lb.in
/
1.5 Nm max.
Solid / Stranded
0.14 mm
2
->
2.5 mm
2
0.27in
/ 6.9mm
PZ2
4.5 lb.in
/
0.5 Nm max.
6.2. Connection to the electrical network and to the loads
The COUNTIS E00/E02 are intended for single-phase networks with neutral.
Pulse output
4: -
5: +
Optocoupler pulse outputs
Terminals 4-5 must be supplied with voltage between 5 and 27
VDC (27 mA max)
Network
L: : Phase input
L': : Phase output
N: Neutral connection
L
L
N
N
4 5
L
L’
40A
N
230 VAC 50/60 Hz
-+