21
EN
ATyS d M - 542 929 C - SOCOMEC
9.
nSTAllATIon oF oPTIonAl ACCeSSoRIeS
9.1. Auxilliary contacts
Ref. 1309 0001 or ref. 1309 0011.
To it an additional AC, the switch must irst be put in the 0 position. An auxiliary contact module comprises: one NO/
NC or NOC changeover contact for each position (I-0-II). To install use the screws supplied with the module.
One module is factory itted.
Pozidriv PZ2 - 1 Nm
Use 35mm
screws for 2
modules
!
Slotted head 3,5 mm
0,45 Nm
0,5 to 2,5 mm²
0,5 to 1,5 mm²
6 mm
9.2.
voltage sensing and power supply tap
Ref. 1399 4006.
This provides 2 connection terminals for conductors with cross-section ≤ 1.5 mm².
The single pole terminals can be itted in any of the terminal cages without reducing the cage connection capacity.
2 parts/ref. Do not use in case of use of the bridging bar.
Slotted head 3,5 mm
0,45 Nm
0,5 to 2,5 mm²
0,5 to 1,5 mm²
6 mm
9.3.
Bridging bars 2P
Ratings ≤ 125A: ref. 1309 2006; 160A : ref. 1309 2016
!
x4
2
4
6
8
1
3
5
7
2
4
6
8
1
3
5
7
/
317 315 314 313
201
202
102 101
2
4
6
8
1
3
5
7
2
4
6
8
1
3
5
7
/
317 315 314 313
201
202
102 101
LOAD
oK
oK
Source II
Hexagonal Metric
Allen size 4
5,0 Nm
Bridging bar.
125A: 1309 2006
160A: 1309 2016
10 to
70 mm²
15mm
There are two references available: one for ratings up to 125A, and another rated at 160A.
On the ATyS d M the bridging bar (load side) may be it to either side of the product (top or bottom).