ATyS d M - 542 929 C - SOCOMEC
13.6.
Possible actions
Once in automatic mode, it is possible to:
• Receive remote order inputs based on impulse or contactor logic.
contactor logic
impulse logic
autoMatic (remote) Mode
13.6.1. Control logic
13.6.1.1. Impulse logic
(Terminal O/C not connected: terminals 313/317 opened; driven when needed)
Impulse logic:
The ATy
S is driven to a stable position (I – O – II) after
receiving an impulse order.
• A switching command of at least 60 ms is
necessary to initiate the switching operation.
• Orders I and II have priority over order 0.
Note: The logic diagrams exclude the transfer times.
Imp. ≥60ms
order I
position I
order 0
position 0
order II
position II
Impulse logic
(Note : Excludes position switching delays)
13.6.1.2. Contactor logic
(Terminal O/C not connected: terminals 313/317 closed; position 0 control maintened)
Contactor logic :
The ATy
S is driven to a speciic position (I or II) for as
long as the order is maintained.
• Order O is maintained. (Bridge 313 – 317)
• Orders I and II have priority over order 0.
• Orders I and II have equal priority.
(1st order received is held until no longer
maintained).
• If order I or II disappears, the device returns to
zero position.
(With the power supply available).
maintened
order I
position I
order 0
position 0
order II
position II
Contactor logic
(Note : Excludes position switching delays)