![Snowflake SBU15HL Service Manual Download Page 48](http://html.mh-extra.com/html/snowflake/sbu15hl/sbu15hl_service-manual_1309837048.webp)
48
765042231 Rev.001
d7 0 15 min
2
2
dripping duration (the compressor and the
evaporator fan remain off during dripping
and the defrosting output will be
deactivated)
d15 0 99
min
0
0
minimum duration of compressor switch-on
on activation of defrosting so these can be
activated (only if parameter d1 is set at 1)
(8)
d16 0 99
min
0
0
duration of pre-dripping (only if parameter
d1 is set at 1; the compressor and
evaporator fan will be off during pre-dripping
and the defrosting output will remain
activated)
Par.
Min.
Max.
Unit
EVX803..02
SBU 15
EVX803..01
SBU 20/40
Temperature alarms (9) (10)
A1 0.0 99.0 °C/°F
(1) 10.0
10.0
cabinet temperature below which the
minimum temperature alarm is activated
(relative to the work set-point, i.e. “r10 - A1”
during post blast chilling storage and “r11 -
A1” during post deep freezing storage; (“AL”
code); also see parameter A11 (4)
A2
0
1
- - - -
1
1
enabling of minimum temperature alarm
(“AL” code)
1 = yes
A4 0.0 99.0 °C/°F
(1) 10.0
10.0
cabinet temperature above which the
maximum temperature alarm is activated
(relative to the work set-point, i.e. “r10 +A4”
during post blast chilling storage and “r11
+A4” during post deep freezing storage;
(“AH” code); also see parameter A11 (4)
A5
0
1
- - - -
1
1
enabling of maximum temperature alarm
(“AH” code)
1 = yes
A7 0 240 min
60
60
temperature alarm delay (“AL” code and
“AH” code)