47
765042231 Rev.001
d1
0
3
- - - -
2
2
type of defrosting
0 = electrical (the compressor will be
switched off during defrosting, the
defrosting output will be activated
and the evaporator fan will be
switched off)
1 = hot gas (the compressor will be
switched on during defrosting, the
defrosting output will be activated
and the evaporator fan will be
switched off)
2 = air (the compressor will be switched
off during defrosting and the
defrosting output will be activated;
the evaporator fan will be switched
on, independently from the
conditions of the door, i.e.
independently from the door micro
switch input status)
3 = air with door open (the compressor
will be switched off during defrosting
and the defrosting output will be
activated; the evaporator fan will be
switched on, on condition that the
door is open, i.e. that is on condition
that the door micro switch is active
and that the parameter i0 is set at
values different to 0)
d2 -50.0 99.0 °C/°F
(1)
8.0
8.0
defrosting end temperature (evaporator
temperature); also see parameter d3
d3 0 99 min
15
15
if parameter P4 is set at 0, duration of
defrosting
if parameter P4 is set at 1, maximum
duration of defrosting; see also parameter
d2
0 = defrosting
will
never be activated
d4
0
1
- - - -
0
0
defrosting on start-up of blast chilling and
deep freezing
1 = yes
d5 0 99 min
0
0
defrosting delay on start-up of storing
0 = defrosting will be started on expiry of
the time established with parameter
d0