Connection of
air
curtains based on BMS communication module
The BMS module for
Ostro air
curtains allows to monitoring the operation of the curtain (EMERGENCY/FAILURE
signal) and switches the curtain on/off from the master BMS system.
With the use of digital signals 0/1 (potential free contact), the BMS
module
can work with any BMS master protocol
without need to convert the signal
8.6
Connection diagram of
100-150-200 W and C with BMS module
SIGNALS FROM BMS
PZ „READY FOR OPERATION”
Digital signal "1" from the master BMS (potential-free contact) - Curtain ready for operation
Digital signal "0" from the master BMS system (potential-free contact open) - Curtain disabled
SIGNALS TO BMS
- MONITORING THE CURTAIN WORK (NOTE - ON/OFF switch on the COMFORT panel in ON position,
"READY FOR OPERATION” signal activated):
PP „OPERATION”
Digital signal "1" (potential-free contact closed) - information about the operation of the curtain
- reed relay on - door
opened
Digital signal "0" (potential-free contact opened)
-
Reed relay off - door closed
If the contactor is not used - after the "OPERATION" signal is applied, the curtain operates continuously in the thermostat
mode - digital signal "1" (potential-free contact closed)
When the curtain is switched off via the thermostat - digital signal "0" (potential-free contact open)
PA „FAILURE”
With proper operation of the curtain - digital signal "0" (potential-free contact opened)
After triggering the fuse C3,15 - digital signal "1" - curtain failure (potential-free contact closed)