2 | SmithsEP.co.uk | Issue 001 - April 2020
Technical manual
Ostro
air curtain v201709
www.sonniger.com
2
1. PURPOSE OF THE DEVICE
Ostro air curtains are designed for use in regions with moderate or cold climates in spaces where the temperature range is -10C to
+40C, in conditions that are free from external contaminants such as pollen and hydrometeor (horizontal precipitation). In winter air
curtains protect against heat loss in rooms by directing a warm air stream across door ways preventing cold air from entering the
heated space. In summer, the air curtains can be used as cooling devices to prevent the entry of hot air and pollutants from the
outside.
The air curtains are designed to protect against heat losses
in buildings of medium and high capacity and with a required
mounting height is of 4 m such as:
supermarkets, large retail space,
car showrooms and service stations,
sports and show halls,
exhibition surfaces
2. BASIC TECHNICAL PARAMETERS
Noise level measured in distance of 3 m in open space building
Parametry
Ostro Curtain with water heater
Ostro Curtain with electric heater
100W
150W
200W
100E
150E
200E
Length of unit
m
1
1.5
2
1
1.5
2
Max. installation height
m
4
4
4
4
4
4
Max air output
m³/h
1200/1550/2000
2200/3000/3600
2900/4000/4800
1200/1550/2000
2200/3000/3600
2900/4000/4800
Heat output
kW
10-16
20-29
25-40
4-7
6.5-11
8.5-14
Max working pressure
MPa
1.6
1.6
1.6
-
-
-
Diameter of connection nozzles
inches
1/2”
1/2”
1/2”
-
-
-
Motor power supply, consumption
V/Hz A
230/50 1.95A
230/50 2.6A
230/50 2.6A
230/50 1.95A
230/50 2.6A
230/50 2.6A
Motor power
kW
51/106/220
75/162/320
75/162/320
51/106/220
75/162/320
75/162/320
Electric heating power supply, consumption
V/Hz A
-
-
-
400/50 11.0A
400/50 16.6A
400/50 22.4A
Weight filled with water/without water
kg
18.0/16.5
22.6/20.5
31.0/28.0
17
21.5
29
Volume level I/II/III*
dB (A)
44/49/59
45/49/61
46/49/61
44/49/59
45/49/61
46/49/61
Protection class IP
-
IP21
IP21
IP21
IP21
IP21
IP21
Parametry
Ostro Curtain without heater
100C
150C
200C
Length of unit
m
1
1.5
2
Max. installation height
m
4
4
4
Max air output
m³/h
1250/1600/2100
2250/3100/3700
3000/4200/5000
Heat output
kW
-
-
-
Max working pressure
MPa
-
-
-
Diameter of connection nozzles
inches
-
-
-
Motor power supply, consumption
V/Hz A
230/50 1.95A
230/50 2.6A
230/50 2.6A
Motor power
kW
51/106/220
75/162/320
75/162/320
Electric heating power supply, consumption
V/Hz A
-
-
-
Weight filled with water/without water
kg
15
18.5
25
Volume level I/II/III*
dB (A)
45/50/60
46/50/61
47/50/61
Protection class IP
-
IP21
IP21
IP21
* Noise level measured in distance of 3m in an open space