Page 4
SERIES 28RTS/HE BOILER INSTALLATION AND OPERATION INSTRUCTIONS
The bottom opening must be within 12 in., 305 mm
of, but not less than 3 in., 76 mm from, the bottom of the
enclosure.
All Air From Outside The Building
When installed in a confi ned space two permanent
openings communicating directly with, or by ducts to,
the outdoors or spaces that freely communicate with
the outdoors must be present. The upper opening must
be within 12 in., 305 mm of, but not less than 3 in.,
76 mm from, the top of the enclosure. The bottom
opening must be within 12 in., 305 mm of, but not less
than 3 in., 76 mm from, the bottom of the enclosure.
Where directly communicating with the outdoors or
communicating with the outdoors through vertical ducts,
each opening shall have a minimum free area of
1 in
2
/4000 Btu/hr, 35 in
2
/GPH, 550 mm
2
/kW of the total
input rating of all of the equipment in the enclosure.
Where communicating with the outdoors through
horizontal ducts, each opening shall have a minimum
free area of 1 in
2
/2000 Btu/hr, 70 in
2
/GPH, 1100 mm
2
/
kW of the total input rating of all of the equipment in the
enclosure. When ducts are used, they must have the
same cross-sectional area as the free area of the
opening to which they connect. When calculating the
free area necessar y to meet the make-up air
requirements of the enclosure, consideration must be
given to the blockage effects of louvers, grills and
screens. Screens must have a minimum mesh size of
1/4 in, 6.4mm. If the free area through a louver or grill
is not known the louver or grille should be sized per
Table 1.
Table 1 - Make-up Air Louver Sizing
Required Cross Sectional Louver Area (in
2
)
Metal
Wooden
Input
1/4", 6.4 mm
Louvers
Louvers
(MBH)
Wire Screen
75% Free Area 25% Free Area
in
2
cm
2
in
2
cm
2
in
2
cm
2
1000
250 1613
333 2148
1000 6452
1200
300 1936 400 2578
1200 7742
1400
350 2258
467 3007
1400 9033
1600
400 2581
533 3437
1600
10,323
1800
450 2903
600 3866
1800
11,614
2000
500
3226
666
4296
2000
12,904
2200
550
3549
733
4726 2200 14,194
2400
600
3871
800
5155
2400
15,485
2600
650
4194
867
5585
2600
16,775
2800
700
4516
934
6014
2800
18,066
3000
750
4838
1000
6452
3000
19,354
3200
800
5162
1066
6874
3200
20,646
3400
850
5484
1134
7303
3400
21,937
3600
900
5807
1200
7733
3600
23,227
3800
950
6129
1267
8162
3800
24,518
4000
1000
6452
1334
8592
4000
25,808
4200
1050
6775
1400
9022
4200
27,098
4400
1100
7097
1467
9451
4400
28,389
4600
1150
7420
1533
9881
4600
29,679
4800
1200
7742
1600
10,310
4800
30,970
COMBUSTION AIR & VENTILATION
WARNING: This boiler must be supplied with
combustion and ventilation air in accordance
with the latest revision of Section 5.3, Air for
Combustion & Ventilation, of the National Fuel
Gas Code, ANSI Z223.1/NFPA 54 for gas boilers
or ANSI/NFPA 31 Installation of Oil Burning
Equipment for oil boilers. Canadian installations
must comply with CAN/CSA B149.1 Natural Gas
and Propane Installation Code for gas boilers
or CSA B140.7 Oil Burning Equipment for oil
boilers. All applicable local building codes
must be adhered to. Failure to provide adequate
combustion air for this boiler can result in
excessive levels of carbon monoxide which can
result in severe personal injury or death!
To operate properly and safely this boiler requires a
continuous supply of air for combustion. An adequate
supply of air must be available to replace the air used
by the combustion process. NEVER store objects on or
around the boiler.
CAUTION: Never use an exhaust fan in the boiler
room. The boiler room must never be under a
negative pressure or improper burner operation will
occur!
NOTE: Forced make-up air supplied to the boiler
room must be approved by the local authorities.
A minimum of 30 ft
3
/GAL, 0.22 m
3
/L for oil or
25 ft
3
/100 MBH (Therm), 0.024 m
3
/kW for gas must be
provided.
All Air From Inside The Buidling
If the boiler is to be located in a confi ned space mini-
mum clearances of 24 in., 610 mm must be maintained
between the boiler and any adjacent construction.
When installed in a confi ned space, two permanent
openings communicating with an additional room(s)
are required. The combined volume of these spaces
must have suffi cient volume to meet the criteria for an
unconfi ned space. The total air requirements of all fuel
burning equipment or any type of exhaust fan must be
considered when making this determination.
Each opening must have a minimum free area of
1 in
2
/1000 Btu/hr, 140 in
2
/GPH, 2200 mm
2
/kW based
on the total input rating of ALL fuel burning equipment
in the confi ned area. Each opening must be no less than
100 in
2
, 64,516 mm
2
in size. The upper opening must be
within 12 in., 305 mm of, but not less than 3 in., 76 mm
from, the top of the enclosure.