BACnet Router Start-up Guide
Page 21 of 27
Appendix A Useful Features
Appendix A.1. Tooltips
Tooltips appear when the mouse pointer hovers over the corresponding settings field. A balloon will
appear giving a description of that input field. This applies to all input fields except Network Settings input
fields.
Parameter
Corresponding Tooltips
IP Address
Configure the IP Address used by BACnet/IP and the web server.
Netmask
Configure the Netmask used by BACnet/IP and the web server.
Default Gateway
Configure the Default Gateway used by BACnet/IP and the web server.
DHCP Client
Note that the IP Address may change and you may need to rediscover the
router if the DHCP Client is enabled.
Network Number
Enter a value between 1 and 65534 that is unique across the entire BACnet
network.
IP Port
The IP Port number to be used for this BACnet/IP connection. Common
values: 47808, 47809.
Device Instance
Enter a value between 0 and 4194302. The Device Instance must be unique
across the entire BACnet network.
Device Name
Enter a name for the Device. The name may not contain any commas.
Device Location
Enter a location for the Device. The location may not contain any commas.
MAC Address
Enter a value between 0 and 127 that is unique for this MS/TP segment.
Max Master
Sets the highest allowable address for MS/TP master nodes on the network.
Set a value between 0 and 127.
Max Info Frames
The number of frames that can be sent by this device during a single token
hold. Set a value between 1 and 100.
Token Usage Timeout (ms) Set a larger value to improve network reliability with slow devices.