QuickServer Start-Up Guide
Page 56 of 60
Appendix D Reference
Appendix D.1. LED Functions
Light Description
SPL
SPL LED will be on when a configured node in the QuickServer is detected as being offline. See
Node overview screen of the FS-GUI for further details.
For LonWorks units
, LED will light until the unit is commissioned on the LonWorks network.
RUN
RUN LED will flash 20 seconds after power up, signifying normal operation. The QuickServer will be
able to access FS-GUI (refer to
Section
6.3
for more information) once this LED starts flashing.
During the first 20 seconds, the LED should be off.
ERR
The ERR LED will go on solid 15 seconds after power up. It will turn off after 5 seconds. A steady red
light will indicate there is a system error on the FieldServer. If this occurs, immediately report the
related “system error” shown in the error screen of the FS-GUI interface to Sierra Monitor for
evaluation.
RX
On normal operation of FS-QS-1XXX, the RX LED will flash when a message is received on the field
port of the QuickServer.
TX
On normal operation of FS-QS-1XXX, the TX LED will flash when a message is sent on the field port
of the QuickServer.
PWR
This is the power light and should show steady green at all times when the QuickServer is powered.
Figure 30: FS-QS-1XXX LEDs