background image

 

QuickServer Start-Up Guide 

Page 39 of 60 

Energy_T_WH_10                  

AI 12 

30023-30024 

Temp_Flow_1                     

AI 13 

30025-30026 

Temp_Ret_1                      

AI 14 

30027-30028 

Time_Hrs_1                      

AI 15 

30029-30030 

Vol_Flo_L_S_1                   

AI 16 

30031-30032 

Error_Flags_1                   

AI 17 

30033-30034 

Medium_1                        

AI 18 

30035-30036 

Medium_2                        

AI 19 

30037-30038 

Volume_1                        

AI 20 

30039-30040 

 

Appendix B.9. Siemens WFH21 Mappings 
to BACnet and Modbus                   

Point Name 

BACnet 

Modbus 

Energy_T_WH_1                   

AI 01 

30001-30002 

Time_Hrs_1                      

AI 02 

30003-30004 

Power_Jh_1                      

AI 03 

30005-30006 

ID_1                            AI 04 

30007-30008 

Volume_1                        

AI 05 

30009-30010 

Volume_2                        

AI 06 

30011-30012 

Unknown_1                       

AI 07 

30013-30014 

Unknown_2                       

AI 08 

30015-30016 

Unknown_3                       

AI 09 

30017-30018 

Unknown_4                       

AI 10 

30019-30020 

 

Appendix B.10. Siemens FUE950 Energy 
Mappings to BACnet and Modbus                   

Point Name 

BACnet 

Modbus 

Energy 1     

AI 01 

30001-30002 

Energy 2     

AI 02 

30003-30004 

Energy 3     

AI 03 

30005-30006 

Energy 4     

AI 04 

30007-30008 

Temp Flow    

AI 05 

30009-30010 

Temp Ret     

AI 06 

30011-30012 

Temp Dif     

AI 07 

30013-30014 

Time Op Days 

AI 08 

30015-30016 

Time Point 1 

AI 09 

30017-30018 

Time Point 2 

AI 10 

30019-30020 

Power        

AI 11 

30021-30022 

Volume Flow  

AI 12 

30023-30024 

Volume 1     

AI 13 

30025-30026 

Volume 2     

AI 14 

30027-30028 

Volume 3     

AI 15 

30029-30030 

Volume 4     

AI 16 

30031-30032 

Firmware     

AI 17 

30033-30034 

Software     

AI 18 

30035-30036 

Access Code  

AI 19 

30037-30038 

 

Appendix B.11. QS All Data Profile 
Mappings to BACnet and Modbus                   

Point Name 

BACnet 

Modbus 

Dur_Avg_S_1     

AI 1 

30001-30002 

Dur_Avg_S_2     

AI 2 

30003-30004 

Dur_Avg_S_3     

AI 3 

30005-30006 

Dur_Avg_S_4     

AI 4 

30007-30008 

Dur_Avg_S_5     

AI 5 

30009-30010 

Dur_Avg_S_6     

AI 6 

30011-30012 

Dur_Avg_S_7     

AI 7 

30013-30014 

Dur_Avg_S_8     

AI 8 

30015-30016 

Dur_Avg_S_9     

AI 9 

30017-30018 

Dur_Avg_S_10    

AI 10 

30019-30020 

Dur_Avg_M_1     

AI 11 

30021-30022 

Dur_Avg_M_2     

AI 12 

30023-30024 

Dur_Avg_M_3     

AI 13 

30025-30026 

Dur_Avg_M_4     

AI 14 

30027-30028 

Dur_Avg_M_5     

AI 15 

30029-30030 

Dur_Avg_M_6     

AI 16 

30031-30032 

Dur_Avg_M_7     

AI 17 

30033-30034 

Dur_Avg_M_8     

AI 18 

30035-30036 

Dur_Avg_M_9     

AI 19 

30037-30038 

Dur_Avg_M_10    

AI 20 

30039-30040 

Dur_Avg_H_1     

AI 21 

30041-30042 

Dur_Avg_H_2     

AI 22 

30043-30044 

Dur_Avg_H_3     

AI 23 

30045-30046 

Dur_Avg_H_4     

AI 24 

30047-30048 

Dur_Avg_H_5     

AI 25 

30049-30050 

Dur_Avg_H_6     

AI 26 

30051-30052 

Dur_Avg_H_7     

AI 27 

30053-30054 

Dur_Avg_H_8     

AI 28 

30055-30056 

Dur_Avg_H_9     

AI 29 

30057-30058 

Dur_Avg_H_10    

AI 30 

30059-30060 

Dur_Avg_D_1     

AI 31 

30061-30062 

Dur_Avg_D_2     

AI 32 

30063-30064 

Dur_Avg_D_3     

AI 33 

30065-30066 

Dur_Avg_D_4     

AI 34 

30067-30068 

Dur_Avg_D_5     

AI 35 

30069-30070 

Dur_Avg_D_6     

AI 36 

30071-30072 

Dur_Avg_D_7     

AI 37 

30073-30074 

Dur_Avg_D_8     

AI 38 

30075-30076 

Dur_Avg_D_9     

AI 39 

30077-30078 

Dur_Avg_D_10    

AI 40 

30079-30080 

Dur_Act_Sec_1   

AI 41 

30081-30082 

Dur_Act_Sec_2   

AI 42 

30083-30084 

Dur_Act_Sec_3   

AI 43 

30085-30086 

Dur_Act_Sec_4   

AI 44 

30087-30088 

Dur_Act_Sec_5   

AI 45 

30089-30090 

Dur_Act_Sec_6   

AI 46 

30091-30092 

Dur_Act_Sec_7   

AI 47 

30093-30094 

Dur_Act_Sec_8   

AI 48 

30095-30096 

Dur_Act_Sec_9   

AI 49 

30097-30098 

Dur_Act_Sec_10  

AI 50 

30099-30100 

Dur_Act_Min_1   

AI 51 

30101-30102 

Dur_Act_Min_2   

AI 52 

30103-30104 

Dur_Act_Min_3   

AI 53 

30105-30106 

Dur_Act_Min_4   

AI 54 

30107-30108 

Dur_Act_Min_5   

AI 55 

30109-30110 

Dur_Act_Min_6   

AI 56 

30111-30112 

Dur_Act_Min_7   

AI 57 

30113-30114 

Dur_Act_Min_8   

AI 58 

30115-30116 

Dur_Act_Min_9   

AI 59 

30117-30118 

Dur_Act_Min_10  

AI 60 

30119-30120 

Dur_Act_Hrs_1   

AI 61 

30121-30122 

Dur_Act_Hrs_2   

AI 62 

30123-30124 

Dur_Act_Hrs_3   

AI 63 

30125-30126 

Dur_Act_Hrs_4   

AI 64 

30127-30128 

Dur_Act_Hrs_5   

AI 65 

30129-30130 

Dur_Act_Hrs_6   

AI 66 

30131-30132 

Dur_Act_Hrs_7   

AI 67 

30133-30134 

Dur_Act_Hrs_8   

AI 68 

30135-30136 

Dur_Act_Hrs_9   

AI 69 

30137-30138 

Dur_Act_Hrs_10  

AI 70 

30139-30140 

Dur_Act_Day_1   

AI 71 

30141-30142 

Dur_Act_Day_2   

AI 72 

30143-30144 

Dur_Act_Day_3   

AI 73 

30145-30146 

Dur_Act_Day_4   

AI 74 

30147-30148 

Dur_Act_Day_5   

AI 75 

30149-30150 

Dur_Act_Day_6   

AI 76 

30151-30152 

Summary of Contents for FS-QS-1010

Page 1: ...Document Revision 2 C T18043 FieldServer QuickServer Start up Guide FS QS 1010 1011 12X0 12X1 1X50 1X51 APPLICABILITY EFFECTIVITY Effective for all systems manufactured after July 2018...

Page 2: ...port needs related to the FieldServer product Sierra Monitor Corporation 1991 Tarob Court Milpitas CA 95035 Website www sierramonitor com U S Support Information 1 408 964 4443 1 800 727 4377 Email su...

Page 3: ...ickServer Over the Ethernet Port 20 6 3 Connecting to the QuickServer 21 6 3 1 Using the FieldServer Toolbox to Discover and Connect to the QuickServer 21 6 3 2 Accessing SMC Cloud 21 6 4 Set IP Addre...

Page 4: ...s 43 Appendix B 16 KromSchroderTRZ2S1 Mappings to BACnet and Modbus 43 Appendix B 17 KromSchroderDE10R25 40B Mappings to BACnet and Modbus 43 Appendix B 18 RelayPadPulsM1 Mappings to BACnet and Modbus...

Page 5: ...12 LonWorks Commissioning and Port 18 Figure 13 KNX Commissioning 18 Figure 14 RS 232 R2 Connection Port 19 Figure 15 Connecting Power 20 Figure 16 Ethernet Port 20 Figure 17 FS GUI Landing Page 21 Fi...

Page 6: ...selected drivers on the FS QS 1X11 and FS QS 12X1 one of those drivers is LonWorks A sample configuration file is also pre loaded onto the QuickServer All instruction manuals driver manuals support u...

Page 7: ...tion about the BACnet Testing Laboratory Click here for the BACnet PIC Statement LonMark International is the recognized authority for certification education and promotion of interoperability standar...

Page 8: ...rt FS 8915 35 QS WARNING Install only as instructed failure to follow the installation guidelines or using screws without the DIN rail mounting bracket could result in permanent damage to the product...

Page 9: ...QuickServer Start Up Guide Page 9 of 60 4 2 Dimensions 4 2 1 Dimension Drawing FS QS 1X10 XXXX R1 Port R2 Port Figure 2 FS QS 1X10 XXXX...

Page 10: ...QuickServer Start Up Guide Page 10 of 60 4 2 2 Dimension Drawing FS QS 1XX1 XXXX LonWorks Port R2 Port Figure 3 FS QS 1XX1 XXXX...

Page 11: ...QuickServer Start Up Guide Page 11 of 60 4 2 3 Dimension Drawing FS QS 123X Models with RS 422 R1 Port R2 Port Figure 4 FS QS 123X models with RS 422...

Page 12: ...help prevent false bits of data from being detected The bias resistors typically pull one line high and the other low far away from the decision point of the logic In the RS 485 carrier the bias resis...

Page 13: ...ation Resistor Termination resistors are also used to reduce noise These pull the two lines of an idle bus together However they would override the effect of any bias resistors if connected Terminatio...

Page 14: ...ther power supply requirements Position A The Carrier makes use of a full wave rectifying bridge Can be used for 12 24VAC input or 9 30VDC input At 9VDC this becomes marginal Position B The Carrier ma...

Page 15: ...er NOTE The following only applies to models FS QS 1A50 FS QS 1A51 FS QS 1B51 FS QS 1B51 FS QS 1C51 and FS QS 1C51 The Master Slave jumper is used to set the M Bus hardware as a Master or Slave device...

Page 16: ...erenced below o The default factory setting is OFF switch position right side o To enable biasing turn the bias switch ON switch position left side NOTE Biasing only needs to be enabled on one device...

Page 17: ...200 38400 57600 115200 For connection details to RS 232 or RS 422 refer to Appendix A 1 5 1 2 RS 485 Connection R1 Port NOTE The following only applies to non LonWorks QuickServers with an RS 435 R1 p...

Page 18: ...sure to access the Service Pin See the instructions on the QuickServer as to which way to toggle the screwdriver during commissioning 5 3 QuickServer KNX FS QS 124X XXXX Connect the QuickServer to the...

Page 19: ...Connection R2 Port only available on FS QS 122X Models Refer to Appendix A2 for further hardware connection options The following Baud Rates are supported on the R2 Port 4800 9600 19200 38400 57600 1...

Page 20: ...ND terminal The QuickServer is factory set for 9 30V DC or 12 24V AC 6 2 Connect the PC to the QuickServer Over the Ethernet Port Connect an Ethernet cable between the PC and QuickServer or connect th...

Page 21: ...f the connect button is greyed out the QuickServer s IP Address must be set to be on the same network as the PC Section 6 4 6 3 2 Accessing SMC Cloud The FieldPoP button see Figure 17 allows users to...

Page 22: ...ld IP Gateway Default Gateway field and DNS 1 2 Domain Name Server fields NOTE If the QuickServer is connected to a router the IP Gateway of the QuickServer should be set to the IP Address of that rou...

Page 23: ...w Subnet Mask If necessary change the IP Gateway Default Gateway field Type in a new IP Gateway NOTE If the FieldServer is connected to a router the IP Gateway of the FieldServer should be set to the...

Page 24: ...evant device registers in the Config csv file for the initial start up If not the product is shipped with a sample config csv that shows an example of the drivers ordered In the main menu of the FS GU...

Page 25: ...the Toolbox main page click on the setup icon the gear picture Select File Transfer Browse and select the csv file open then click Update Config Once download is complete click the Restart Button or...

Page 26: ...d finally Update Browse and select the csv file open then click Submit Once download is complete a message bar will appear confirming that the configuration was updated successfully Click the System R...

Page 27: ...menu of the FS GUI screen click Setup then File Transfer Click the config csv link under the Retrieve heading in the middle section of the screen o The file will automatically download to the web bro...

Page 28: ...the QuickServer Connect the QuickServer to the third party device s and test the application From the landing page of the FS GUI click on View in the navigation tree then Connections to see the numbe...

Page 29: ...r to peer high speed communication when low bus latency is required very few devices on the bus Its usage is very specific to client installations requirements NOTE The RS 232 looks similar to the RS...

Page 30: ...ignals may be crossed Pin 5 SHD Shield connection must be connected on at least one side of the bus but not necessarily on both sides POWER Connector Please note that AC voltage is not supported on th...

Page 31: ...arms etc This allows BMS systems to access a KNX network using direct read and write or with KNX configured groups This setup does not require the use of ETS4 to configure the QuickServer KNX gateway...

Page 32: ...kServer Gateway is configurable to act as both a Master and a Slave M Bus device The M Bus Connector consist of a and terminal Most M Bus Devices are not polarity sensitive although the polarity of th...

Page 33: ...ollowing example sets the FieldServer to accept a secure Modbus TCP connection on port 1502 Appendix A 4 1 1 Simple Secure Server Configuration Add TLS_Port parameter in the connections section of the...

Page 34: ...ldServer with the following connection settings Connections Adapter Protocol TLS_Port Validate_Client_Cert Cert_Authority_File N1 Modbus TCP 1502 Yes my_authorized_clients pem This configuration has t...

Page 35: ...ymously known as common name host name or domain etc The common name can be obtained by the following methods Ask the certificate issuer for the host name Use online tools to decode the certificate fo...

Page 36: ...rtificate against its own internal authority file before finalizing the connection By default this means the FieldServer will only establish connections to other FieldServers Remote_Node_TLS_Port Vali...

Page 37: ...5 30016 RH_Avg AI 09 30017 30018 Appendix B 4 EMU 3PH Power 3 85 Mappings to BACnet and Modbus Point Name BACnet Modbus MBUS_Meter_ node_id_Alarms AI 01 30001 30002 Energy_WH_1 AI 02 30003 30004 Energ...

Page 38: ...Vol_Flo_L_H_1 AI 36 30071 30072 Vol_Flo_L_H_2 AI 37 30073 30074 Vol_Flo_L_H_3 AI 38 30075 30076 Vol_Flo_L_H_4 AI 39 30077 30078 Vol_Flo_L_H_5 AI 40 30079 30080 Vol_Flo_L_H_6 AI 41 30081 30082 Vol_Flo...

Page 39: ...Avg_M_4 AI 14 30027 30028 Dur_Avg_M_5 AI 15 30029 30030 Dur_Avg_M_6 AI 16 30031 30032 Dur_Avg_M_7 AI 17 30033 30034 Dur_Avg_M_8 AI 18 30035 30036 Dur_Avg_M_9 AI 19 30037 30038 Dur_Avg_M_10 AI 20 30039...

Page 40: ...AI 142 30283 30284 Temp_Ret_3 AI 143 30285 30286 Temp_Ret_4 AI 144 30287 30288 Temp_Ret_5 AI 145 30289 30290 Temp_Ret_6 AI 146 30291 30292 Temp_Ret_7 AI 147 30293 30294 Temp_Ret_8 AI 148 30295 30296 T...

Page 41: ...Pressure_9 AI 279 30557 30558 Pressure_10 AI 280 30559 30560 Mass_1 AI 281 30561 30562 Mass_2 AI 282 30563 30564 Mass_3 AI 283 30565 30566 Mass_4 AI 284 30567 30568 Mass_5 AI 285 30569 30570 Mass_6 A...

Page 42: ...0818 Alarm_Flags_10 AI 410 30819 30820 Appendix B 12 Kamstrup 66 Mappings to BACnet and Modbus Point Name BACnet Modbus Energy_T_WH_1 AI 01 30001 30002 Energy_T_WH_2 AI 02 30003 30004 Energy_T_WH_3 AI...

Page 43: ..._Avg_D_4 AI 034 30067 30068 Dur_Avg_D_5 AI 035 30069 30070 Dur_Avg_D_6 AI 036 30071 30072 Dur_Avg_D_7 AI 037 30073 30074 Dur_Avg_D_8 AI 038 30075 30076 Dur_Avg_D_9 AI 039 30077 30078 Dur_Avg_D_10 AI 0...

Page 44: ...6 Time_Sec_4 AI 164 30327 30328 Time_Sec_5 AI 165 30329 30330 Time_Sec_6 AI 166 30331 30332 Time_Sec_7 AI 167 30333 30334 Time_Sec_8 AI 168 30335 30336 Time_Sec_9 AI 169 30337 30338 Time_Sec_10 AI 170...

Page 45: ...ol_Flo_L_M_1 AI 301 30601 30602 Vol_Flo_L_M_2 AI 302 30603 30604 Vol_Flo_L_M_3 AI 303 30605 30606 Vol_Flo_L_M_4 AI 304 30607 30608 Vol_Flo_L_M_5 AI 305 30609 30610 Vol_Flo_L_M_6 AI 306 30611 30612 Vol...

Page 46: ...re 1 AI 16 30031 30032 Flow Temperature 2 AI 17 30033 30034 Flow Temperature 3 AI 18 30035 30036 Return Temperature 1 AI 19 30037 30038 Return Temperature 2 AI 20 30039 30040 Return Temperature 3 AI 2...

Page 47: ...0177 30178 Fabrication Number 1 AI 90 30179 30180 Fabrication Number 2 AI 91 30181 30182 Fabrication Number 3 AI 92 30183 30184 Appendix B 23 Kamstrup Multical Mappings to BACnet and Modbus Point Name...

Page 48: ...3 30134 Volume Flow 6 AI 68 30135 30136 Volume Flow 7 AI 69 30137 30138 Volume Flow 8 AI 70 30139 30140 Volume Flow 9 AI 71 30141 30142 Volume 1 AI 72 30143 30144 Volume 2 AI 73 30145 30146 Volume 3 A...

Page 49: ...stom_1 AI 5 30009 30010 Power_W_1 AI 6 30011 30012 Pressure_1 AI 7 30013 30014 Mass_1 AI 8 30015 30016 Vol_Flo_L_M_1 AI 9 30017 30018 Volume_1 AI 10 30019 30020 Unknown_1 AI 11 30021 30022 Unknown_2 A...

Page 50: ...Dif_3 AI 19 30037 30038 Time_Op_Hrs_1 AI 20 30039 30040 Time_Op_Hrs_2 AI 21 30041 30042 Time_Op_Hrs_3 AI 22 30043 30044 Power_W_1 AI 23 30045 30046 Power_W_2 AI 24 30047 30048 Power_W_3 AI 25 30049 30...

Page 51: ...etwork If using Windows XP or later ensure that the firewall is disabled Appendix C 2 Before Contacting Technical Support Take a Diagnostic Capture When a problem occurs that cannot be resolved with r...

Page 52: ...Start Up Guide Page 52 of 60 Step 1 Take a Log o Click on the diagnose icon of the desired device o Ensure Full Diagnostic is selected this is the default NOTE If desired the default capture period ca...

Page 53: ...d is finished the Diagnostic Test Complete window will appear Step 2 Send Log o Once the diagnostic test is complete a zip file will be saved on the PC o Click Open to launch explorer and have it poin...

Page 54: ...he Diagnostic Capture is complete email it to technical support The Diagnostic Capture will accelerate diagnosis of the problem Open the FieldServer FS GUI page Click on Diagnostics in the Navigation...

Page 55: ...sword on the FS GUI Passwords page click Setup and then Passwords in the navigation panel There are 2 access levels defined by 2 account names Admin and User The Admin account has unrestricted access...

Page 56: ...ashing During the first 20 seconds the LED should be off ERR The ERR LED will go on solid 15 seconds after power up It will turn off after 5 seconds A steady red light will indicate there is a system...

Page 57: ...SNMP BACnet IP 1047 SNMP LonWorks 1178 SNMP JCI Metasys N2 1154 SNMP BACnet MS TP 1200 BACnet MS TP LonWorks 0345 Appendix D 3 QuickServer Part Numbers Field Connections Interface Connections RS 2321...

Page 58: ...y with local electrical code o Be suited to the expected operating temperature range o Meet the current and voltage rating for ProtoNode Net Furthermore the interconnecting power cable shall o Be of l...

Page 59: ...Temperature 40 C to 75 C 40 F to167 F Surge Suppression EN61000 4 2 ESD EN61000 4 3 EMC EN61000 4 4 EFT Humidity 5 90 RH non condensing Figure 31 Specifications This device complies with part 15 of t...

Page 60: ...or on which original identification marks have been removed or altered This Limited Warranty also will not apply to interconnecting cables or wires consumables or to any damage resulting from battery...

Reviews: