QuickServer Start-Up Guide
Page 10 of 43
4.3 Connecting the R1 Port
For the R1 Port only:
Switch between RS-485 and RS-232 by moving the number 4 DIP Switch left for
RS-485 and right for RS-232 (
The R2 Port is RS-485.
Connect to the 3-pin connector(s) as shown below.
4.3.1 Wiring
RS-485
RS-232
BMS RS-485
Wiring
Gateway Pin
Assignment
BMS RS-232
Wiring
Gateway Pin
Assignment
RS-485 +
TX +
RS-232 -
TX +
RS-485 -
RX -
RS-232 +
RX -
GND
GND
GND
GND
NOTE: Use standard grounding principles for GND.
4.3.2 Supported RS-485 Baud Rates by Protocol
The supported baud rates for either port is based on the protocol of the connected devices.
The following baud rates are supported for Modbus RTU:
2400, 4800, 9600, 19200, 38400, 57600, 76800, 115200
The following baud rates are supported for BACnet MS/TP:
9600, 19200, 38400, 76800
TX+ RX- GND
+
-
GND
Figure 5: R1 & R2 Connection Ports