background image

 

Stulz Driver Manual 

Page 10 of 16 

APPENDIX A. STULZ COMMANDS 

FieldServer as a Client

 

Command 

Description 

Data Type  Signed 

Range 

Units 

C6000 

Active Commands 

ls 

Long state request 

Byte 

 

m1fss 

Module 1 fan speed setpoint 

Integer 

0..100 

r/w 

m2fss 

Module 2 fan speed setpoint 

Integer 

0..100 

r/w 

m3fss 

Module 3 fan speed setpoint 

Integer 

0..100 

r/w 

m4fss 

Module 4 fan speed setpoint 

Integer 

0..100 

r/w 

m5fss 

Module 5 fan speed setpoint 

Integer 

0..100 

r/w 

m6fss 

Module 6 fan speed setpoint 

Integer 

0..100 

r/w 

m1dcsst 

Module 1 drycooler summer start 

Integer 

0..50 

r/w 

m1dcwst 

Module 1 drycooler winter start 

Integer 

0..30 

r/w 

m2dcsst 

Module 2 drycooler summer start 

Integer 

0..50 

r/w 

m2dcwst 

Module 2 drycooler winter start 

Integer 

0..30 

r/w 

m3dcsst 

Module 3 drycooler summer start 

Integer 

0..50 

r/w 

m3dcwst 

Module 3 drycooler winter start 

Integer 

0..30 

r/w 

m4dcsst 

Module 4 drycooler summer start 

Integer 

0..50 

r/w 

m4dcwst 

Module 4 drycooler winter start 

Integer 

0..30 

r/w 

m5dcsst 

Module 5 drycooler summer start 

Integer 

0..50 

r/w 

m5dcwst 

Module 5 drycooler winter start 

Integer 

0..30 

r/w 

m6dcsst 

Module 6 drycooler summer start 

Integer 

0..50 

r/w 

m6dcwst 

Module 6 drycooler winter start 

Integer 

0..30 

r/w 

ssat 

Setpoint Supply Air Temperature 

Float 

10..35 

r/w 

ssah 

Setpoint Supply Air Humidity 

Integer 

0..100 

r/w 

ssrt 

Setpoint Room Temperature 

Float 

10..35 

r/w 

ssrt 

Setpoint Room Humidity 

Integer 

0..100 

r/w 

hpdsc 

HP DSC Function 

Integer 

– DSCwFS 

– Stulz 

2 - DSC 

r/w 

gcwmode 

G/CW mode 

Byte 

 

0..1 

r/w 

cwsel 

Remote CW selector 

Byte 

 

0..1 

r/w 

rfs1 

Read Fan Speed 1 

Float 

0..100 

r/w 

rfs2 

Read Fan Speed 2 

Float 

0..100 

r/w 

rfs3 

Read Fan Speed 3 

Float 

0..100 

r/w 

Passive_Client Commands 

wt       

Water temperature 

Float 

-50..50 

rat      

Return air temperature 

Float 

0..100 

sat      

Supply air temperature 

Float 

0..100 

rah      

Return air humidity 

Float 

0..100 

sah      

Supply air humidity 

Float 

0..100 

oat      

Outside air temperature 

Float 

-50..50 

oah      

Outside air humidity 

Float 

0..100 

tss      

Temperature set point shift 

Float 

-12.7..12.7 

hss      

Humidity set point shift 

Float 

-12.7..12.7 

swv      

Software version 

  

  

  

  

m1o1     

Module 1 digital out status byte 1 

Uint16 

  

  

  

Reheat 1 

Bit 

  

  

  

Compressor 1 

Bit 

  

  

  

Humidification 1 

Bit 

  

  

  

Dehumidification 1 

Bit 

  

  

  

Fan 1 

Bit 

  

  

  

Dry cooler 

Bit 

  

  

  

Alarm relays 1 (1= no alarm) 

Bit 

  

  

  

PWW 

Bit 

  

  

  

m1o2     

Module 1 digital out status byte 2 

Uint16 

  

  

  

Reheat 2 

Bit 

  

  

  

Glycol pump 

Bit 

  

  

  

Louver (0=closed, 1=open) 

Bit 

  

  

  

Alarm relays 2 (1= no alarm) 

Bit 

  

  

  

Alarm relays 3 (1= no alarm) 

Bit 

  

  

  

Alarm relays 4 (1= no alarm) 

Bit 

  

  

  

Alarm relays 5 (1= no alarm) 

Bit 

  

  

  

Summary of Contents for FieldServer FS-8700-125 Stulz

Page 1: ...evision 1 01 Document Revision 2 B FieldServer FS 8700 125 Stulz Driver Manual Supplement to the FieldServer Instruction Manual APPLICABILITY EFFECTIVITY Effective for all systems manufactured after J...

Page 2: ...t needs related to the FieldServer product Sierra Monitor Corporation 1991 Tarob Court Milpitas CA 95035 Website www sierramonitor com U S Support Information 1 408 964 4443 1 800 727 4377 Email suppo...

Page 3: ...ient Side Connection Parameters 7 4 2 Client Side Node Parameters 8 4 3 Client Side Map Descriptor Parameters 8 4 3 1 FieldServer Related Map Descriptor Parameters 8 4 3 2 Driver Specific Map Descript...

Page 4: ...s supported as the protocol only specifies read capabilities on that unit The Client is configurable to read all information into separate data points and supports writing to selected points as specif...

Page 5: ...onnection Tips Hints Connect the wire to bus 1 on the Stulz device Make sure that bus 1 is used as bus 2 is used by the device to communicate with its IO devices Use shielded twisted pair wire to make...

Page 6: ...alues Data_Array_Name Provide name for Data Array Up to 15 alphanumeric characters Data_Array_Format Provide data format Each Data Array can only take on one format Float Bit Byte Uint16 Uint32 Sint16...

Page 7: ...eeds to be declared in the Nodes section and the data to be provided to the Clients needs to be mapped in the Map Descriptors section Details on how to do this can be found below NOTE In the tables be...

Page 8: ...p Descriptor Up to 32 alphanumeric characters Data_Array_Name Name of Data Array where data is to be stored in the FieldServer One of the Data Array names from Section 3 Data_Array_Offset Starting loc...

Page 9: ...gth Scan_Interval sett 1 5 Example comments Data_Array_Name This Data Array is where the data will be stored and to which a write can be performed if it is supported see Appendix A Function These comm...

Page 10: ...winter start Integer N 0 30 C r w ssat Setpoint Supply Air Temperature Float N 10 35 C r w ssah Setpoint Supply Air Humidity Integer N 0 100 r w ssrt Setpoint Room Temperature Float N 10 35 C r w ssrt...

Page 11: ...yte 1 Uint16 r m3i25 Module 3 digital in status byte 2 Uint16 r m4i14 Module 4 digital in status byte 1 Uint16 r m4i25 Module 4 digital in status byte 2 Uint16 r m5i14 Module 5 digital in status byte...

Page 12: ...pressure Bit r 4 not used Bit r 5 not used Bit r 6 not used Bit r 7 not used Bit r sett Setpoint temperature Float N 10 35 C r w seth Setpoint humidity Integer N 10 90 r w year Date Year Integer N 0 9...

Page 13: ...90 r w 2hums Humidification start Integer N 0 90 r w 2humh Humidification hysteresis Integer N 0 90 r w 2humsa Humidification start analogue Integer N 0 90 r w 2humpba Humidification proportional band...

Page 14: ...midification start Integer N 0 90 r w 5humh Humidification hysteresis Integer N 0 90 r w 5humsa Humidification start analogue Integer N 0 90 r w 5humpba Humidification proportional band Integer N 0 90...

Page 15: ...humid Too high alarm Bit r 4 water temp too high alarm Bit r 5 return air temp too low alarm Bit r 6 return air humid Too low alarm Bit r 7 supply air temp too low alarm Bit r err2 Error byte 2 Uint1...

Page 16: ...Stulz Driver Manual Page 16 of 16 APPENDIX B TROUBLESHOOTING Driver Limitations Only the 9600 baud setting is supported by Stulz devices...

Reviews: