Stulz Driver Manual 

Page 11 of 16 

FieldServer as a Client

 

Command 

Description 

Data Type  Signed 

Range 

Units 

C6000 

Glycol pump 1/2 select 

Bit 

  

  

  

m2o1

2

 

Module 2 digital out status byte 1 

Uint16 

  

  

  

m2o2

3

     

Module 2 digital out status byte 2 

Uint16 

  

  

  

m3o1

2

     

Module 3 digital out status byte 1 

Uint16 

  

  

  

m3o2

3

     

Module 3 digital out status byte 2 

Uint16 

  

  

  

m4o1

2

     

Module 4 digital out status byte 1 

Uint16 

  

  

  

m4o2

3

     

Module 4 digital out status byte 2 

Uint16 

  

  

  

m5o1

2

     

Module 5 digital out status byte 1 

Uint16 

  

  

  

m5o2

3

     

Module 5 digital out status byte 2 

Uint16 

  

  

  

m6o1

2

     

Module 6 digital out status byte 1 

Uint16 

  

  

  

m6o2

3

     

Module 6 digital out status byte 2 

Uint16 

  

  

  

m1i1     

Module 1 digital in status byte 1 

Uint16 

  

  

  

Compressor low pressure 

Bit 

  

  

  

Compressor high pressure 

Bit 

  

  

  

Reheat 1 failure 

Bit 

  

  

  

Humidification failure 

Bit 

  

  

  

Air flow failure 

Bit 

  

  

  

Filter clogged 

Bit 

  

  

  

Aux alarm 1 

Bit 

  

  

  

Reheat 2 alarm 

Bit 

  

  

  

m1i2     

Module 1 digital in status byte 2 

Uint16 

  

  

  

Conductivity too high 

Bit 

  

  

  

Ultrasonic failure 

Bit 

  

  

  

Glycol pump 1 failure 

Bit 

  

  

  

Glycol pump 2 failure 

Bit 

  

  

  

Drycooler failure 

Bit 

  

  

  

Water detector 

Bit 

  

  

  

Aux alarm 2 

Bit 

  

  

  

Aux alarm 3 

Bit 

  

  

  

m2i1

4

     

Module 2 digital in status byte 1 

Uint16 

  

  

  

m2i2

    

Module 2 digital in status byte 2 

Uint16 

  

  

  

m3i1

    

Module 3 digital in status byte 1 

Uint16 

  

  

  

m3i2

5

     

Module 3 digital in status byte 2 

Uint16 

  

  

  

m4i1

4

     

Module 4 digital in status byte 1 

Uint16 

  

  

  

m4i2

5

     

Module 4 digital in status byte 2 

Uint16 

  

  

  

m5i1

4

     

Module 5 digital in status byte 1 

Uint16 

  

  

  

m5i2

5

     

Module 5 digital in status byte 2 

Uint16 

  

  

  

m6i1

4

     

Module 6 digital in status byte 1 

Uint16 

  

  

  

m6i2

5

     

Module 6 digital in status byte 2 

Uint16 

  

  

  

m1gecw   

Module 1 analogue out GE/CW 

Float 

0..100 

  

m2gecw   

Module 2 analogue out GE/CW 

Float 

0..100 

  

m3gecw   

Module 3 analogue out GE/CW 

Float 

0..100 

  

m4gecw   

Module 4 analogue out GE/CW 

Float 

0..100 

  

m5gecw   

Module 5 analogue out GE/CW 

Float 

0..100 

  

m6gecw   

Module 6 analogue out GE/CW 

Float 

0..100 

  

m1pww    

Module 1 analogue out PWW 

Float 

0..100 

  

m2pww    

Module 2 analogue out PWW 

Float 

0..100 

  

m3pww    

Module 3 analogue out PWW 

Float 

0..100 

  

m4pww    

Module 4 analogue out PWW 

Float 

0..100 

  

m5pww    

Module 5 analogue out PWW 

Float 

0..100 

  

m6pww    

Module 6 analogue out PWW 

Float 

0..100 

  

m1aoh    

Module 1 analogue out humidifier 

Float 

0..100 

  

m2aoh    

Module 2 analogue out humidifier 

Float 

0..100 

  

m3aoh    

Module 3 analogue out humidifier 

Float 

0..100 

  

m4aoh    

Module 4 analogue out humidifier 

Float 

0..100 

  

m5aoh    

Module 5 analogue out humidifier 

Float 

0..100 

  

m6aoh    

Module 6 analogue out humidifier 

Float 

0..100 

  

                                                      

2

 

These commands’ structure match the m1o1 structure. 

3

 

These commands’ structure match the m1o2 structure. 

4

 These c

ommands’ structure match the m1i1 structure. 

5

 

These commands’ structure match the m1i2 structure.

 

Summary of Contents for FieldServer FS-8700-125 Stulz

Page 1: ...evision 1 01 Document Revision 2 B FieldServer FS 8700 125 Stulz Driver Manual Supplement to the FieldServer Instruction Manual APPLICABILITY EFFECTIVITY Effective for all systems manufactured after J...

Page 2: ...t needs related to the FieldServer product Sierra Monitor Corporation 1991 Tarob Court Milpitas CA 95035 Website www sierramonitor com U S Support Information 1 408 964 4443 1 800 727 4377 Email suppo...

Page 3: ...ient Side Connection Parameters 7 4 2 Client Side Node Parameters 8 4 3 Client Side Map Descriptor Parameters 8 4 3 1 FieldServer Related Map Descriptor Parameters 8 4 3 2 Driver Specific Map Descript...

Page 4: ...s supported as the protocol only specifies read capabilities on that unit The Client is configurable to read all information into separate data points and supports writing to selected points as specif...

Page 5: ...onnection Tips Hints Connect the wire to bus 1 on the Stulz device Make sure that bus 1 is used as bus 2 is used by the device to communicate with its IO devices Use shielded twisted pair wire to make...

Page 6: ...alues Data_Array_Name Provide name for Data Array Up to 15 alphanumeric characters Data_Array_Format Provide data format Each Data Array can only take on one format Float Bit Byte Uint16 Uint32 Sint16...

Page 7: ...eeds to be declared in the Nodes section and the data to be provided to the Clients needs to be mapped in the Map Descriptors section Details on how to do this can be found below NOTE In the tables be...

Page 8: ...p Descriptor Up to 32 alphanumeric characters Data_Array_Name Name of Data Array where data is to be stored in the FieldServer One of the Data Array names from Section 3 Data_Array_Offset Starting loc...

Page 9: ...gth Scan_Interval sett 1 5 Example comments Data_Array_Name This Data Array is where the data will be stored and to which a write can be performed if it is supported see Appendix A Function These comm...

Page 10: ...winter start Integer N 0 30 C r w ssat Setpoint Supply Air Temperature Float N 10 35 C r w ssah Setpoint Supply Air Humidity Integer N 0 100 r w ssrt Setpoint Room Temperature Float N 10 35 C r w ssrt...

Page 11: ...yte 1 Uint16 r m3i25 Module 3 digital in status byte 2 Uint16 r m4i14 Module 4 digital in status byte 1 Uint16 r m4i25 Module 4 digital in status byte 2 Uint16 r m5i14 Module 5 digital in status byte...

Page 12: ...pressure Bit r 4 not used Bit r 5 not used Bit r 6 not used Bit r 7 not used Bit r sett Setpoint temperature Float N 10 35 C r w seth Setpoint humidity Integer N 10 90 r w year Date Year Integer N 0 9...

Page 13: ...90 r w 2hums Humidification start Integer N 0 90 r w 2humh Humidification hysteresis Integer N 0 90 r w 2humsa Humidification start analogue Integer N 0 90 r w 2humpba Humidification proportional band...

Page 14: ...midification start Integer N 0 90 r w 5humh Humidification hysteresis Integer N 0 90 r w 5humsa Humidification start analogue Integer N 0 90 r w 5humpba Humidification proportional band Integer N 0 90...

Page 15: ...humid Too high alarm Bit r 4 water temp too high alarm Bit r 5 return air temp too low alarm Bit r 6 return air humid Too low alarm Bit r 7 supply air temp too low alarm Bit r err2 Error byte 2 Uint1...

Page 16: ...Stulz Driver Manual Page 16 of 16 APPENDIX B TROUBLESHOOTING Driver Limitations Only the 9600 baud setting is supported by Stulz devices...