background image

 

Stulz Driver Manual 

Page 15 of 16 

FieldServer as a Client

 

Command 

Description 

Data Type  Signed 

Range 

Units 

C6000 

gst2

6    

 

General status byte 2 

Uint16 

  

  

  

  

G/CW-mode; G:1, CW:0 

Bit 

  

  

  

r/w 

CW-Valve OR/AND 

– selector 

Bit 

  

  

  

not used  

  

  

  

  

  

not used  

  

  

  

  

  

not used  

  

  

  

  

  

not used  

  

  

  

  

  

not used  

  

  

  

  

  

not used  

  

  

  

  

  

err1     

Error byte 1 

Uint16 

  

  

  

  

return air temp. too high alarm 

Bit 

  

  

  

return air humid. Too high alarm 

Bit 

  

  

  

supply air temp. too high alarm 

Bit 

  

  

  

supply air humid. Too high alarm 

Bit 

  

  

  

water temp. too high alarm 

Bit 

  

  

  

return air temp. too low alarm 

Bit 

  

  

  

return air humid. Too low alarm 

Bit 

  

  

  

supply air temp. too low alarm 

Bit 

  

  

  

err2     

Error byte 2 

Uint16 

  

  

  

  

supply air humid. Too low alarm 

Bit 

  

  

  

water temp. too low alarm 

Bit 

  

  

  

supervisor failure 

Bit 

  

  

  

freeze alarm 

Bit 

  

  

  

fire / smoke detector 

Bit 

  

  

  

sensor failure 

Bit 

  

  

  

controller failure 

Bit 

  

  

  

IO-board transmission failure 

Bit 

  

  

  

ar

7

 

Alarm reset 

None 

 

 

 

 
 

 

                                                      

6

 This command has been replaced by gcwmode and cwsel to enable write on the second bit (V2.66). 

7

 Writing any value to this command will reset the alarms on the Stulz unit.

 

Summary of Contents for FieldServer FS-8700-125 Stulz

Page 1: ...evision 1 01 Document Revision 2 B FieldServer FS 8700 125 Stulz Driver Manual Supplement to the FieldServer Instruction Manual APPLICABILITY EFFECTIVITY Effective for all systems manufactured after J...

Page 2: ...t needs related to the FieldServer product Sierra Monitor Corporation 1991 Tarob Court Milpitas CA 95035 Website www sierramonitor com U S Support Information 1 408 964 4443 1 800 727 4377 Email suppo...

Page 3: ...ient Side Connection Parameters 7 4 2 Client Side Node Parameters 8 4 3 Client Side Map Descriptor Parameters 8 4 3 1 FieldServer Related Map Descriptor Parameters 8 4 3 2 Driver Specific Map Descript...

Page 4: ...s supported as the protocol only specifies read capabilities on that unit The Client is configurable to read all information into separate data points and supports writing to selected points as specif...

Page 5: ...onnection Tips Hints Connect the wire to bus 1 on the Stulz device Make sure that bus 1 is used as bus 2 is used by the device to communicate with its IO devices Use shielded twisted pair wire to make...

Page 6: ...alues Data_Array_Name Provide name for Data Array Up to 15 alphanumeric characters Data_Array_Format Provide data format Each Data Array can only take on one format Float Bit Byte Uint16 Uint32 Sint16...

Page 7: ...eeds to be declared in the Nodes section and the data to be provided to the Clients needs to be mapped in the Map Descriptors section Details on how to do this can be found below NOTE In the tables be...

Page 8: ...p Descriptor Up to 32 alphanumeric characters Data_Array_Name Name of Data Array where data is to be stored in the FieldServer One of the Data Array names from Section 3 Data_Array_Offset Starting loc...

Page 9: ...gth Scan_Interval sett 1 5 Example comments Data_Array_Name This Data Array is where the data will be stored and to which a write can be performed if it is supported see Appendix A Function These comm...

Page 10: ...winter start Integer N 0 30 C r w ssat Setpoint Supply Air Temperature Float N 10 35 C r w ssah Setpoint Supply Air Humidity Integer N 0 100 r w ssrt Setpoint Room Temperature Float N 10 35 C r w ssrt...

Page 11: ...yte 1 Uint16 r m3i25 Module 3 digital in status byte 2 Uint16 r m4i14 Module 4 digital in status byte 1 Uint16 r m4i25 Module 4 digital in status byte 2 Uint16 r m5i14 Module 5 digital in status byte...

Page 12: ...pressure Bit r 4 not used Bit r 5 not used Bit r 6 not used Bit r 7 not used Bit r sett Setpoint temperature Float N 10 35 C r w seth Setpoint humidity Integer N 10 90 r w year Date Year Integer N 0 9...

Page 13: ...90 r w 2hums Humidification start Integer N 0 90 r w 2humh Humidification hysteresis Integer N 0 90 r w 2humsa Humidification start analogue Integer N 0 90 r w 2humpba Humidification proportional band...

Page 14: ...midification start Integer N 0 90 r w 5humh Humidification hysteresis Integer N 0 90 r w 5humsa Humidification start analogue Integer N 0 90 r w 5humpba Humidification proportional band Integer N 0 90...

Page 15: ...humid Too high alarm Bit r 4 water temp too high alarm Bit r 5 return air temp too low alarm Bit r 6 return air humid Too low alarm Bit r 7 supply air temp too low alarm Bit r err2 Error byte 2 Uint1...

Page 16: ...Stulz Driver Manual Page 16 of 16 APPENDIX B TROUBLESHOOTING Driver Limitations Only the 9600 baud setting is supported by Stulz devices...