-26-
No.PS
※※
-OMU0012-A
•
[F 2] Setting of OUT2
Item
Explanation
Default setting
Output mode
Either hysteresis mode, window comparator mode, error output
or switch output OFF can be selected.
Hysteresis mode
Reversed output
Selects which type of switch output is used, normal or reversed.
Normal output
Pressure setting
Sets the ON and OFF point of the switch output.
0.500 MPa
Hysteresis
Appropriate setting of the hysteresis will prevent the switch
output from chattering.
0.050 MPa
Delay time
Delay time of the switch output can be selected.
1.0 ms or less
Display colour
Select the display colour.
Output ON : Green
Output OFF: Red
(Linked to OUT)
•
Other parameter settings
Item
Page
Default setting
[F 3] Digital filter setting
Page
0 ms
[F 4] Auto-preset function
Page
Not used
[F 5]
-
No configurable items
[F 6] Fine adjustment of display value
Page
0
%
[F10] Sub display setting
Page
std (Standard)
[F11] Display resolution setting
Page
1000-split
[F80] Power saving mode
Page
OFF
[F81] Security code
Page
OFF
[F82] Input of line name
Page
AAAA
[F90] Setting of all functions
Page
OFF
[F96]
-
No configurable items
[F97]
-
No configurable items
[F98] Output check
Page
N/A (normal output)
[F99] Reset to default settings
Page
OFF