-14-
No.PS
※※
-OMU0012-A
■
Wiring
•Connections should be made with the power supply turned off.
•Use a separate route for the product wiring and any power or high voltage wiring.
Otherwise, malfunction may result due to noise.
•If a commercially available switching power supply is used, be sure to ground the frame ground (FG)
terminal. If the switching power supply is connected for use, switching noise will be superimposed and it
will not be able to meet the product specifications. In that case, insert a noise filter such as a line noise
filter/ferrite between the switching power supplies or change the switching power supply to the series
power supply.
○Wiring connections
•Align the body connector key and the cable connector key groove to insert vertically and rotate the
knurled part on the cable side.
•Check that the connection is not loose.
•Power supply/ output connector pin No. (M12 plug connector on body side)
Pin No.
Description
1
DC(+)
2
OUT2
3
DC(-)
4
OUT1
•Sensor connector pin No. (M12 socket connector on body side)
Description
Part No.
PSE300AC
PSE310AC
PSE310AC
Pin No.
Pressure sensor 3-wire type
Pressure sensor
2-wire type
1
DC(+)
LINE(+)
2
N.C.
N.C.
3
DC(-)
N.C.
4
Sensor input: 1 to 5 V Sensor input: 4 to 20 mA
LINE(-)
5
N.C.
N.C.