IO-Link Specifications
■
Outline of IO-Link functions
○
Communication function
This product can check the pressure measurement value, diagnostic information and switch output status
using cyclic data communication via the IO-Link system.
○
Product status monitoring function
This function monitors the product status via the IO-Link communication.
•Detects the error status (internal hardware error).
•Detects the warning conditions (product internal temperature error, measurement pressure error).
○
Data storage function
The Data storage function stores the IO-Link device parameter settings to the IO-Link master.
With the IO-Link data storage function, the IO-Link device can be replaced easily without re-setting the
equipment construction or setting parameters
When the device parameters are set and downloaded to the device using the IO-Link setting tool, the
parameters in the downloaded device will be activated.
After that, these parameters are uploaded to the data storage in the master by stem command (back-up
communication command).
When the device is replaced with the same type of IO-Link device due to failure, the parameter settings
stored in the master are downloaded automatically, device can be operated with the parameter settings of
the previous device.
Device parameter setting is applicable to 3 types of back-up levels of the master setting ("Inactive",
"back-up/Restore", "Restore").
"Back-up" implies the activation of upload and "restore" implies download.
■
Communication specifications
IO-Link type
Device
IO-Link version
V1.1
Communication speed
COM2 (38.4 kbps)
Min. cycle time
2.3 ms
Process data length
Input Data: 2 byte, Output Data: 0 byte
On request data communication
Available
Data storage function
Available
Event function
Available
Summary of Contents for ISE20CH-L
Page 96: ...95 No PS OMX0002 Dimensions 02 type...
Page 97: ...96 No PS OMX0002 F02 type C01 type A2 type B2 type...
Page 98: ...97 No PS OMX0002 02L type...
Page 99: ...98 No PS OMX0002 F02L type C01L type A2L type B2L type...
Page 100: ...99 No PS OMX0002 Bracket mounting dimensions Bracket A...
Page 101: ...100 No PS OMX0002 Bracket C...
Page 103: ...102 No PS OMX0002 Mounting dimensions of panel mount adapter bottom piping type...
Page 106: ...105 No PS OMX0002 Vertical...