ISDU parameters
Index
(dec)
Sub
index
Access
∗
1
Parameters
Initial value
Remarks
0x0002
(2)
0
W
System command
-
Refer to "System command"
on page
0x000C
(12)
0
R/W
Device access lock
0x0000
Refer to "Device access lock
parameters" on page 68.
0x0010
(16)
0
R
Vendor name
SMC Corporation
0x0011
(17)
0
R
Vendor text
www.smcworld.com
0x0012
(18)
0
R
Product name
Example:
ISE20B-L
0x0013
(19)
0
R
Product ID
Example:
ISE20B-L
0x0014
(20)
0
R
Product text
Pressure sensor
0x0015
(21)
0
R
Serial number
Example:
"xxxxxxxx"
•Initial value is indicated as 8-digit.
•16 octets fixed character string
0x0016
(22)
0
R
Hardware version
HW-Vx.y
x: Large revision number
y: Small revision number
0x0017
(23)
0
R
Software version
FW-Vx.y
x: Large revision number
y: Small revision number
0x0024
(36)
0
R
Device status
parameter
-
Refer to "Device state parameters"
on page
0x0025
(37)
0
R
Device detailed
state parameter
-
Refer to "Device detail status
parameters" on page
0x0028
(40)
0
R
Process data input
-
The latest value of process data
can be read.
∗
1: R: Read, W: Wright
●
System command (index 2)
In the ISDU index 0x002 SystemCommand (system command), the command shown in the table below
will be issued.
The button of each system command is displayed on the IO-Link setting tool (excluding
"ParamDownloadStore").
Click the button to send the system command to the product.
Writable commands are shown below.
Data type: 8 bit UInteger
Value (dec)
Function definition
Description
0x80(128)
Device Reset
Restarts the device
0x81(129)
Application Reset
Clears peak/bottom value
0x82(130)
Restore Factory Settings
Restores factory default values
0xA0(160)
Zero Clear
Executes zero clear